Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 19, 2019, 10:18 AM
  • Section#4_08 0468_08 0467__8192019__I0221.mp4

Date
08/19/2019
W/O
0787221
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00026
PipeID
P00524
Time
3:18 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0221
Sewer Name
08 216TH STREET TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Capital Improvement Program Assesment
Project
20190819MDM_216TH_STREET_TRUNK
Material
RCP-CTL
Shape
Circular
Height
36 in.
Upstream MH
08 0468
Downstream MH
08 0467
Dir. of Survey
Downstream
Length Surveyed
440.3 ft.
Total Length
440.3 ft.
Structural Index
5
Structural Quick
5a4Q
Structural Rating
1202
O&M Index
5
O&M Quick
5441
O&M Rating
24
Overall Index
5
Overall Quick
Overall Rating
1226
Pipe schematic from manhole 08 0468 to 08 0467
MH: 08 0468MH: 08 0467downstream0 ft. MWM - Water Mark, 80 %of cross sectional area0 ft. MGO - General Observation - MH CONN 9:00 OPEN0 ft. MWL - Water Level, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:45AM2 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - AREAS OF MISSING TILES2 ft. MGO - General Observation - 80% MISSING TILES START2 ft. MGO - General Observation - 90% MAG COAT START 10:00 TO 2:003 ft. DSZ - Deposits Settled Other, 50 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: NO, Start - MISSING TILES UNDER FLOW14.5 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR BROKEN & MISSING19.5 ft. DSZ - Deposits Settled Other, 50 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: NO, Finish - MISSING TILES34.1 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR MISSING63.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR107.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR BROKEN134.5 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CORRISON BEYOUND REBAR149.2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR174.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR220.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR227.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR257.4 ft. MGO - General Observation - 30% MISSING TILES START289.6 ft. MGO - General Observation - 100% MISSING TILES304.7 ft. MGO - General Observation - 90% MISSING TILES START354.2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO362 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR BROKEN & MISSING362 ft. MWM - Water Mark, 50 %of cross sectional area362 ft. MWL - Water Level, 30 %of cross sectional area440.3 ft. MGO - General Observation - MH CONN 3:00 OPEN440.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CORRISION BEYOUND REBAR440.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - LONG & CIRCUM REBAR BROKEN & MISSING440.3 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG AREAS OF MISSING TILES440.3 ft. AMH - Downstream Manhole, Survey Ends - 5:30AM440.3 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - LONG & CIRCUM REBAR BROKEN & MISSING440.3 ft. MGO - General Observation - 90% MISSING TILES FINISH440.3 ft. MGO - General Observation - MH CONN 12:00 OPEN440.3 ft. MGO - General Observation - 90% MAG COAT FINISH

Observation photos (18)

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - AREAS OF MISSING TILES

    2 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - AREAS OF MISSING TILES

  • General Observation - 80%  MISSING TILES START

    2 ft. - General Observation - 80% MISSING TILES START

  • General Observation - 90% MAG COAT START 10:00 TO 2:00

    2 ft. - General Observation - 90% MAG COAT START 10:00 TO 2:00

  • Deposits Settled Other,  50 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: NO, Start - MISSING TILES UNDER FLOW

    3 ft. - Deposits Settled Other, 50 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: NO, Start - MISSING TILES UNDER FLOW

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR BROKEN & MISSING

    14.5 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR BROKEN & MISSING

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR MISSING

    34.1 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR MISSING

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR

    63.6 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR BROKEN

    107.6 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR BROKEN

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CORRISON BEYOUND REBAR

    134.5 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CORRISON BEYOUND REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

    149.2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

  • Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR

    174.7 ft. - Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

    220.7 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

    227.6 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

  • General Observation - 30% MISSING TILES START

    257.4 ft. - General Observation - 30% MISSING TILES START

  • General Observation - 100% MISSING TILES

    289.6 ft. - General Observation - 100% MISSING TILES

  • General Observation - 90% MISSING TILES START

    304.7 ft. - General Observation - 90% MISSING TILES START

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO

    354.2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR BROKEN & MISSING

    362 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR BROKEN & MISSING

Observations (34)

DistanceCodeObservation
257.4MGO30% MISSING TILES START
440.3MGOMH CONN 3:00 OPEN
149.2SRCBROKEN REBAR
440.3SRCCORRISION BEYOUND REBAR
14.5SRCLONG & CIRCUM REBAR BROKEN & MISSING
2SAMAREAS OF MISSING TILES
440.3SRCLONG & CIRCUM REBAR BROKEN & MISSING
440.3SAMSEVERE AGG AREAS OF MISSING TILES
440.3AMH5:30AM
63.6SRCLONG & CIRCUM REBAR
0MWM
440.3SRCLONG & CIRCUM REBAR BROKEN & MISSING
220.7SRCBROKEN REBAR
174.7SRCBROKEN REBAR
0MGOMH CONN 9:00 OPEN
362SRCLONG & CIRCUM REBAR BROKEN & MISSING
19.5DSZMISSING TILES
304.7MGO90% MISSING TILES START
2MGO80% MISSING TILES START
0MWL
227.6SRCBROKEN REBAR
440.3MGO90% MISSING TILES FINISH
362MWM
440.3MGOMH CONN 12:00 OPEN
354.2SRC
362MWL
440.3MGO90% MAG COAT FINISH
107.6SRCCIRCUM REBAR BROKEN
2MGO90% MAG COAT START 10:00 TO 2:00
134.5SRCCORRISON BEYOUND REBAR
289.6MGO100% MISSING TILES
34.1SRCLONG & CIRCUM REBAR MISSING
3DSZMISSING TILES UNDER FLOW
0AMH4:45AM

Properties (6)

custom_field_three
REBAR BROKEN & MISSING - CORRISON BEYOUND REBAR
custom_field_two
1
customer
LACSD
datetime
2019-08-19T03:18:31-07:00
documentation
MARTIN,REVELES,OLIVER 111,BRAR
is_lateral_inspection
false