Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 4, 2019, 07:17 AM
  • 14 0654_14 0653 _06042019_003557.mp4

Date
06/04/2019
W/O
671823
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00568
PipeID
P18743
Time
12:17 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6550
Sewer Name
14 AMARGOSA CREEK TRUNK
City
LANCASTER
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
22
Purpose
Routine Assessment
Project
WO_671823_TV14005_MAY2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
14 0654
Downstream MH
14 0653
Dir. of Survey
Downstream
Length Surveyed
376.1 ft.
Total Length
376.1 ft.
Structural Index
2
Structural Quick
2N00
Structural Rating
150
O&M Index
2
O&M Quick
2N00
O&M Rating
152
Overall Index
2
Overall Quick
Overall Rating
302
Pipe schematic from manhole 14 0654 to 14 0653
MH: 14 0654MH: 14 0653downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 06542 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start98.6 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"103.2 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"333.7 ft. TBA - Tap Break-In Active, at 04 o'clock, -, within 8 inches of joint: NO, 6", 6"350.6 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"361.2 ft. OBJ - Obstacles In Joint, 10 %of cross sectional area, from 12 to 06 o'clock374.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish375 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish376.1 ft. AMH - Downstream Manhole, Survey Ends - 14 0653

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Obstacles In Joint, 10 %of cross sectional area, from 12 to 06 o'clock

    361.2 ft. - Obstacles In Joint, 10 %of cross sectional area, from 12 to 06 o'clock

Observations (13)

DistanceCodeObservation
333.7TBA
2DAGS
103.2TBA
350.6TBA
0MWL
376.1AMH14 0653
0MWM
374.9DAGS
98.6TFA
375SSS
0AMH14 0654
2SSS
361.2OBJ

Properties (7)

additional_info
SC378165
custom_field_two
4
customer
LACSD
datetime
2019-06-04T00:17:48-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
31748