Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 3, 2019, 10:12 AM
  • 14 0683_14 0682 _06032019_032944.mp4

Date
06/03/2019
W/O
671823
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00568
PipeID
P18772
Time
3:12 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6549
Sewer Name
14 AMARGOSA CREEK TRUNK
City
LANCASTER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
28
Purpose
Routine Assessment
Project
WO_671823_TV14005_MAY2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
14 0683
Downstream MH
14 0682
Dir. of Survey
Downstream
Length Surveyed
398.7 ft.
Total Length
398.7 ft.
Structural Index
3
Structural Quick
3O2O
Structural Rating
395
O&M Index
2
O&M Quick
2_00
O&M Rating
316
Overall Index
2
Overall Quick
Overall Rating
711
Pipe schematic from manhole 14 0683 to 14 0682
MH: 14 0683MH: 14 0682downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 06832 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start2 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start61.1 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 6" - open396.2 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish396.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish397 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish397 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish398.7 ft. AMH - Downstream Manhole, Survey Ends - 14 0682

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
397SSS
2DAGS
2DAZ
61.1TFAopen
0MWM
397CM
2SSS
396.2DAZ
0MWL
398.7AMH14 0682
0AMH14 0683
396.2DAGS
2CM

Properties (7)

additional_info
SC378164
custom_field_two
4
customer
LACSD
datetime
2019-06-03T03:12:42-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
31748