Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 13, 2019, 09:40 AM
  • 14 0668_14 0667 _06132019_025328.mp4

Date
06/13/2019
W/O
671823
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00568
PipeID
P18757
Time
2:40 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6606
Sewer Name
14 AMARGOSA CREEK TRUNK
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
23
Purpose
Routine Assessment
Project
WO_671823_TV14005_MAY2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
14 0667
Downstream MH
14 0668
Dir. of Survey
Upstream
Length Surveyed
255.7 ft.
Total Length
255.7 ft.
Structural Index
2
Structural Quick
2I00
Structural Rating
100
O&M Index
2
O&M Quick
2I00
O&M Rating
100
Overall Index
2
Overall Quick
Overall Rating
200
Pipe schematic from manhole 14 0667 to 14 0668
MH: 14 0667MH: 14 0668upstream0 ft. AMH - Upstream Manhole, Survey Ends - 14 06680.7 ft. MGO - General Observation - CONN IN MH @ 12 O'CLOCK/CAPPED2.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish96.7 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN253.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start253.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start255.7 ft. AMH - Downstream Manhole, Survey Begins - 14 0667255.7 ft. MWM - Water Mark, 15 %of cross sectional area255.7 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
253SSS
2DAGS
0AMH14 0667
255.7AMH14 0668
255MGOCONN IN MH @ 12 O'CLOCK/CAPPED
253DAGS
159TBOPEN
0MWM
0MWL
2SSS

Properties (7)

additional_info
SC378172
custom_field_two
4
customer
LACSD
datetime
2019-06-13T02:40:57-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
31748