Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 14, 2019, 05:06 AM
  • 14 0669_14 0668 _06132019_222758.mp4

Date
06/13/2019
W/O
671823
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00568
PipeID
P18758
Time
10:06 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6607
Sewer Name
14 AMARGOSA CREEK TRUNK
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
23
Purpose
Routine Assessment
Project
WO_671823_TV14005_MAY2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
14 0669
Downstream MH
14 0668
Dir. of Survey
Downstream
Length Surveyed
318.8 ft.
Total Length
318.8 ft.
Structural Index
2
Structural Quick
2L00
Structural Rating
126
O&M Index
2
O&M Quick
2L00
O&M Rating
126
Overall Index
2
Overall Quick
Overall Rating
252
Pipe schematic from manhole 14 0669 to 14 0668
MH: 14 0669MH: 14 0668downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 06690 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start55 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN156.1 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"317 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish318 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 6" - IN MH318.8 ft. AMH - Downstream Manhole, Survey Ends - 14 0668318.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
0MWM
318.8AMH14 0668
2DAGS
0AMH14 0669
0MWL
318TFCIN MH
156.1TBA
318.8DAGS
2SSS
317SSS
55TBOPEN

Properties (7)

additional_info
SC378173
custom_field_two
4
customer
LACSD
datetime
2019-06-13T22:06:13-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
31748