Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 3, 2019, 09:17 AM
  • 14 0684_14 0683 _06032019_023420.mp4

Date
06/03/2019
W/O
671823
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00568
PipeID
P18773
Time
2:17 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6549
Sewer Name
14 AMARGOSA CREEK TRUNK
City
LANCASTER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
28
Purpose
Routine Assessment
Project
WO_671823_TV14005_MAY2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
14 0684
Downstream MH
14 0683
Dir. of Survey
Downstream
Length Surveyed
400.3 ft.
Total Length
400.3 ft.
Structural Index
3
Structural Quick
3O2O
Structural Rating
395
O&M Index
2
O&M Quick
2400
O&M Rating
8
Overall Index
2
Overall Quick
Overall Rating
403
Pipe schematic from manhole 14 0684 to 14 0683
MH: 14 0684MH: 14 0683downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 06840 ft. MWM - Water Mark, 10 %of cross sectional area2 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start - MINERALS2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start37.8 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"398 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish398 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish399.2 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish399.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish400.3 ft. AMH - Downstream Manhole, Survey Ends - 14 0683

Observation photos (2)

  • Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start - MINERALS

    2 ft. - Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start - MINERALS

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
399.2DAZ
0MWL
37.8TFC
2DAZMINERALS
398SSS
399.2DAGS
2DAGS
2SSS
0AMH14 0684
400.3AMH14 0683
398CM
2CM
0MWM

Properties (7)

additional_info
SC378164
custom_field_two
4
customer
LACSD
datetime
2019-06-03T02:17:40-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
31748