Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 26, 2019, 09:25 AM
  • 15 0789_15 0788 _02262019_012939.mp4

Date
02/26/2019
W/O
750672
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00593
PipeID
P12990
Time
1:25 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6405
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
ARCADIA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_750672_TV15146_FEB2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0788
Downstream MH
15 0789
Dir. of Survey
Upstream
Length Surveyed
324.3 ft.
Total Length
324.3 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
192
O&M Index
2
O&M Quick
2L00
O&M Rating
128
Overall Index
3
Overall Quick
Overall Rating
320
Pipe schematic from manhole 15 0788 to 15 0789
MH: 15 0788MH: 15 0789upstream0 ft. AMH - Upstream Manhole, Survey Ends - 15 07890.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish5.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"89 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"314.8 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"322.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start322.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start324.3 ft. MWM - Water Mark, 20 %of cross sectional area324.3 ft. AMH - Downstream Manhole, Survey Begins - 15 0788324.3 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
9.5TB
0MWM
2DAGS
235.3TF
323.5SAP
319.2TFC
324.3AMH15 0789
2SAP
0AMH15 0788
323.5DAGS
0MWL

Properties (6)

additional_info
SC365920
custom_field_two
2
customer
LACSD
datetime
2019-02-26T01:25:40-08:00
documentation
PRO PIPE
is_lateral_inspection
false