Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 26, 2019, 10:16 AM
  • 15 0779_15 0778 _02262019_021642.mp4

Date
02/26/2019
W/O
750672
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00593
PipeID
P12980
Time
2:16 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6405
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_750672_TV15146_FEB2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0779
Downstream MH
15 0778
Dir. of Survey
Downstream
Length Surveyed
195.9 ft.
Total Length
195.9 ft.
Structural Index
3
Structural Quick
3G00
Structural Rating
114
O&M Index
2
O&M Quick
2G00
O&M Rating
76
Overall Index
3
Overall Quick
Overall Rating
190
Pipe schematic from manhole 15 0779 to 15 0778
MH: 15 0779MH: 15 0778downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 15 07792 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start76.9 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"103.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"117.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"121.6 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"159.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"194.4 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish194.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish195.9 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK195.9 ft. AMH - Downstream Manhole, Survey Ends - 15 0778

Observation photos (2)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
0MWL
2SAP
0MWM
194.4SAP
121.6TBA
195.9MGOACTIVE CONNECTION AT MH 3 O'CLOCK
76.9TFC
117.8TFC
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
2DAGS
195.9AMH15 0778
103.3TFA
0AMH15 0779
194.4DAGS
159.4TFA

Properties (6)

additional_info
SC365920
custom_field_two
2
customer
LACSD
datetime
2019-02-26T02:16:27-08:00
documentation
PRO PIPE
is_lateral_inspection
false