Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 17, 2019, 05:58 PM
  • 15 0265_15 0264_06172019_111636.mp4

Date
06/17/2019
W/O
766400
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00627
PipeID
P12188
Time
10:58 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6655
Sewer Name
15 SAN JOSE CREEK TRUNK
City
INDUSTRY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
37
Purpose
Routine Assessment
Project
WO_766400_TV15133_MAY2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
15 0265
Downstream MH
15 0264
Dir. of Survey
Downstream
Length Surveyed
304.3 ft.
Total Length
304.3 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
177
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
182
Pipe schematic from manhole 15 0265 to 15 0264
MH: 15 0265MH: 15 0264downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 02650 ft. MWL - Water Level, 35 %of cross sectional area0 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH0 ft. MWM - Water Mark, 75 %of cross sectional area7.9 ft. MGO - General Observation - MAGNEZIUM H.O COATING start8 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start102 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"199.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"288.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"301.5 ft. MGO - General Observation - MAGNEZIUM H.O COATING finish301.5 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish304.3 ft. AMH - Downstream Manhole, Survey Ends - 15 0264

Observation photos (2)

  • General Observation - MAGNEZIUM H.O COATING start

    7.9 ft. - General Observation - MAGNEZIUM H.O COATING start

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    8 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
288.4TFC
102TFC
199.5TFC
0AMH15 0265
301.5MGOMAGNEZIUM H.O COATING finish
0MWL
8SAV
301.5SAV
7.9MGOMAGNEZIUM H.O COATING start
304.3AMH15 0264
0MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
0MWM

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-06-17T10:58:31-07:00
documentation
PROPIPE
is_lateral_inspection
false