Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 10, 2019, 03:00 PM
  • 15 0222_15 0221_06102019_035236.mp4

Date
06/10/2019
W/O
766400
Weather
Dry
Operator/Surveyor
J. VARGAS
Sewer ID
Z00627
PipeID
P12144
Time
8:00 AM
Certificate
U-209-8149
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6604
Sewer Name
15 SAN JOSE CREEK TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
01
Purpose
Routine Assessment
Project
WO_766400_TV15133_MAY2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
15 0222
Downstream MH
15 0221
Dir. of Survey
Downstream
Length Surveyed
242 ft.
Total Length
242 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 15 0222 to 15 0221
MH: 15 0222MH: 15 0221downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 02220 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK ABANDONED0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK ACTIVE2.6 ft. MGO - General Observation - MAG COAT THROUGHOUT REACH2.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start238.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish238.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish238.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish242 ft. AMH - Downstream Manhole, Survey Ends - 15 0221242 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (4)

  • General Observation - MAG COAT THROUGHOUT REACH

    2.6 ft. - General Observation - MAG COAT THROUGHOUT REACH

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
238.4SAP
0AMH15 0222
2.6MGOMAG COAT THROUGHOUT REACH
238.4SSS
242AMH15 0221
238.4DAGS
0MWL
242MGOCONNECTION AT MH 9 O'CLOCK
0MWM
2.6SSS
2.6SAP
2.6DAGS
0MGOCONNECTION AT MH 3 O'CLOCK ABANDONED
0MGOCONNECTION AT MH 9 O'CLOCK ACTIVE

Properties (6)

additional_info
SC377526
custom_field_two
3
customer
LACSD
datetime
2019-06-10T08:00:31-07:00
documentation
PRO PIPE
is_lateral_inspection
false