Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 17, 2019, 04:36 PM
  • 15 0262_15 0261_06172019_095807.mp4

Date
06/17/2019
W/O
766400
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00627
PipeID
P12185
Time
9:36 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6655
Sewer Name
15 SAN JOSE CREEK TRUNK
City
INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
34
Purpose
Routine Assessment
Project
WO_766400_TV15133_MAY2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
15 0262
Downstream MH
15 0261
Dir. of Survey
Downstream
Length Surveyed
412.9 ft.
Total Length
412.9 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole 15 0262 to 15 0261
MH: 15 0262MH: 15 0261downstream0 ft. MWM - Water Mark, 75 %of cross sectional area0 ft. MWL - Water Level, 70 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 02623.7 ft. MGO - General Observation - MAGNEZIUM H.O COATING start3.7 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start97.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"194 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"307.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"364.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"410.3 ft. MGO - General Observation - MAGNEZIUM H.O COATING finish410.3 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish412.9 ft. AMH - Downstream Manhole, Survey Ends - 15 0261412.9 ft. MGO - General Observation - CAPPED CONNECTION AT 3 O' CLOCK AT MH

Observation photos (2)

  • General Observation - MAGNEZIUM H.O COATING start

    3.7 ft. - General Observation - MAGNEZIUM H.O COATING start

  • Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    3.7 ft. - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
412.9AMH15 0261
0MWM
0MWL
194TFA
0AMH15 0262
307.6TFC
410.3MGOMAGNEZIUM H.O COATING finish
410.3SAV
97.1TFC
364.7TFC
3.7MGOMAGNEZIUM H.O COATING start
3.7SAV
412.9MGOCAPPED CONNECTION AT 3 O' CLOCK AT MH

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-06-17T09:36:17-07:00
documentation
PROPIPE
is_lateral_inspection
false