Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 11, 2019, 03:00 PM
  • 15 0233_15 0232A_06112019_015326.mp4

Date
06/11/2019
W/O
766400
Weather
Dry
Operator/Surveyor
J. VARGAS
Sewer ID
Z00627
PipeID
P12155
Time
8:00 AM
Certificate
U-209-8149
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6603
Sewer Name
15 SAN JOSE CREEK TRUNK
City
INDUSTRY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
33
Purpose
Routine Assessment
Project
WO_766400_TV15133_MAY2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
15 0233
Downstream MH
15 0232A
Dir. of Survey
Downstream
Length Surveyed
454.9 ft.
Total Length
454.9 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
2111
O&M Rating
3
Overall Index
2
Overall Quick
Overall Rating
8
Pipe schematic from manhole 15 0233 to 15 0232A
MH: 15 0233MH: 15 0232Adownstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 02336.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start6.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.9 ft. MGO - General Observation - MAG COAT THROUGHOUT REACH7.7 ft. VC - Vermin Cockroach207.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"404.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"451.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish451.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish451.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish454.9 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK ACTIVE454.9 ft. AMH - Downstream Manhole, Survey Ends - 15 0232A

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    6.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.9 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COAT THROUGHOUT REACH

    6.9 ft. - General Observation - MAG COAT THROUGHOUT REACH

Observations (15)

DistanceCodeObservation
6.9DAGS
0MWL
6.9SAP
0MWM
7.7VC
454.9MGOCONNECTION AT MH 9 O'CLOCK ACTIVE
451.4DAGS
207.6TFC
451.4SAP
454.9AMH15 0232A
6.9SSS
404.6TFC
6.9MGOMAG COAT THROUGHOUT REACH
451.4SSS
0AMH15 0233

Properties (6)

additional_info
SC377527
custom_field_two
3
customer
LACSD
datetime
2019-06-11T08:00:45-07:00
documentation
PRO PIPE
is_lateral_inspection
false