Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 19, 2018, 03:38 PM
  • 18 0107_18 0106 _23072018_015002.mpg

Date
07/19/2018
W/O
716712
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00698
PipeID
P13927
Time
8:38 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5320
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
WO_716712_TV18177_JUL2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0107
Downstream MH
18 0106
Dir. of Survey
Downstream
Length Surveyed
310.2 ft.
Total Length
310.2 ft.
Structural Index
3
Structural Quick
483L
Structural Rating
235
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
235
Pipe schematic from manhole 18 0107 to 18 0106
MH: 18 0107MH: 18 0106downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Downstream Manhole, Survey Begins - 18 01070 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area6.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"9.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"39.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES40.4 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES42.6 ft. CH2 - Crack Longitudinal Hinge, 2, from 03 to 09 o'clock, within 8 inches of joint: YES, Start56.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"59.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"84.3 ft. CH2 - Crack Longitudinal Hinge, 2, from 03 to 09 o'clock, within 8 inches of joint: YES, Finish107.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"110.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"159.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"162.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"185.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start208.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"211.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"217.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish257.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"260.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"307.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish310.2 ft. AMH - Downstream Manhole, Survey Ends - 18 0106

Observation photos (5)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    39.2 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    40.4 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal Hinge, 2, from 03 to 09 o'clock, within 8 inches of joint: YES, Start

    42.6 ft. - Crack Longitudinal Hinge, 2, from 03 to 09 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    185.6 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

Observations (25)

DistanceCodeObservation
211.6TFA
6.1SAP
0MGOCONNECTION AT MH 3 O'CLOCK
260.6TFC
6.1TFA
257.1TF
307.2SAP
0AMH18 0107
162.9TFC
159.1TFA
107.7TFA
84.3CH2
56.2TFC
59.4TFC
40.4CL
208.6TFA
0MWL
110.5TFC
42.6CH2
0MWM
185.6FL
310.2AMH18 0106
39.2FL
217.7FL
9.7TFC

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2018-07-19T08:38:15-07:00
documentation
PROPIPE
is_lateral_inspection
false