Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 24, 2018, 05:26 AM
  • 18 0089_18 0088 _23072018_224525.mpg

Date
07/23/2018
W/O
716712
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00698
PipeID
P13908
Time
10:26 PM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5321
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
WO_716712_TV18177_JUL2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0089
Downstream MH
18 0088
Dir. of Survey
Downstream
Length Surveyed
357 ft.
Total Length
357 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
207
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
211
Pipe schematic from manhole 18 0089 to 18 0088
MH: 18 0089MH: 18 0088downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 00896.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start61.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"162.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"203.6 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 12 to 04 o'clock, , within 8 inches of joint: YES257.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"274.9 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 02 o'clock, , within 8 inches of joint: YES353.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish357 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK357 ft. AMH - Downstream Manhole, Survey Ends - 18 0088

Observation photos (3)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.8 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 12 to 04 o'clock,  , within 8 inches of joint: YES

    203.6 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 12 to 04 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 02 o'clock,  , within 8 inches of joint: YES

    274.9 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 02 o'clock, , within 8 inches of joint: YES

Observations (12)

DistanceCodeObservation
6.8SAP
257.5TFC
0MWM
61.3TFC
0MWL
353.4SAP
274.9DAE
357MGOCONNECTION AT MH 3 O'CLOCK
203.6DAE
0AMH18 0089
357AMH18 0088
162.4TFC

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2018-07-23T22:26:07-07:00
documentation
PROPIPE
is_lateral_inspection
false