Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 24, 2018, 07:41 AM
  • 18 0084_18 0083 _24072018_005825.mpg

Date
07/24/2018
W/O
716712
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00698
PipeID
P13903
Time
12:41 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5321
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
WO_716712_TV18177_JUL2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0084
Downstream MH
18 0083
Dir. of Survey
Downstream
Length Surveyed
390.5 ft.
Total Length
390.5 ft.
Structural Index
3
Structural Quick
3O00
Structural Rating
234
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
234
Pipe schematic from manhole 18 0084 to 18 0083
MH: 18 0084MH: 18 0083downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 00840 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area4.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start10.7 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"88.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"93.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"93.4 ft. CM - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES160.4 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"280.3 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"347.8 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"387.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish390.5 ft. AMH - Downstream Manhole, Survey Ends - 18 0083

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.4 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

    93.4 ft. - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

Observations (13)

DistanceCodeObservation
0AMH18 0084
88.4TFC
4.4SAP
347.8TFA
0MWL
280.3TFA
390.5AMH18 0083
0MWM
93.2TFA
93.4CM
10.7TFA
160.4TFA
387.3SAP

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2018-07-24T00:41:55-07:00
documentation
PROPIPE
is_lateral_inspection
false