Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 24, 2018, 07:59 AM
  • 18 0083_18 0082 _24072018_012022.mpg

Date
07/24/2018
W/O
716712
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00698
PipeID
P13902
Time
12:59 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5321
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
WO_716712_TV18177_JUL2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0083
Downstream MH
18 0082
Dir. of Survey
Downstream
Length Surveyed
386.8 ft.
Total Length
386.8 ft.
Structural Index
3
Structural Quick
3O00
Structural Rating
237
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
237
Pipe schematic from manhole 18 0083 to 18 0082
MH: 18 0083MH: 18 0082downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 00830 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.2 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES16.7 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"104.7 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"118.2 ft. CM - Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES152.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6"246.3 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"250.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"307 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"372.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES384 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish386.8 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK386.8 ft. AMH - Downstream Manhole, Survey Ends - 18 0082

Observation photos (4)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    6.2 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

    118.2 ft. - Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    372.9 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (16)

DistanceCodeObservation
386.8MGOCONNECTION AT MH 9 O'CLOCK
0AMH18 0083
6SAP
246.3TFA
386.8AMH18 0082
118.2CM
0MWM
0MWL
307TFA
152.1TF
384SAP
104.7TFA
372.9CM
6.2CM
16.7TFA
250.8TFC

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2018-07-24T00:59:29-07:00
documentation
PROPIPE
is_lateral_inspection
false