- Date
- 07/24/2018
- W/O
- 716712
- Weather
- Dry
- Operator/Surveyor
- E.RUIZ
- Sewer ID
- Z00698
- PipeID
- P13895
- Time
- 2:42 AM
- Certificate
- U-715-07000753
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K5321
- Sewer Name
- 18 SANTA FE STREET TRUNK
- City
- WHITTIER
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 18
- Page No.
- 21
- Purpose
- Routine Assessment
- Project
- WO_716712_TV18177_JUL2018
- Sewer Type
- Gravity
- Material
- NRCP
- Shape
- Circular
- Height
- 15 in.
- Width
- 15 in.
- Upstream MH
- 18 0077
- Downstream MH
- 18 1096
- Dir. of Survey
- Upstream
- Length Surveyed
- 235.2 ft.
- Total Length
- 235.2 ft.
- Structural Index
- 4
- Structural Quick
- 4G39
- Structural Rating
- 183
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 4
- Overall Quick
- —
- Overall Rating
- 183
Pipe schematic from manhole 18 0077 to 18 1096 Observation photos (5)

7.8 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

34.9 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES

35 ft. - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6"

105.1 ft. - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

124.8 ft. - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES