Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 24, 2018, 08:55 AM
  • 18 0425_18 0076 _24072018_021146.mpg

Date
07/24/2018
W/O
716712
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00698
PipeID
P13893
Time
1:55 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5321
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
WO_716712_TV18177_JUL2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0425
Downstream MH
18 0076
Dir. of Survey
Downstream
Length Surveyed
222.5 ft.
Total Length
222.5 ft.
Structural Index
4
Structural Quick
4H32
Structural Rating
178
O&M Index
1
O&M Quick
3122
O&M Rating
13
Overall Index
4
Overall Quick
Overall Rating
191
Pipe schematic from manhole 18 0425 to 18 0076
MH: 18 0425MH: 18 0076downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 04250 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7 ft. SAM - Surface Aggregate Missing, from 11 to 01 o'clock, within 8 inches of joint: YES12.1 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start12.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish34.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 12 to 03 o'clock, , within 8 inches of joint: YES61.5 ft. ID - Infiltration Dripper, from 11 to 01 o'clock, within 8 inches of joint: YES82.8 ft. RFJ - Roots Fine Joint, from 07 to 11 o'clock, within 8 inches of joint: YES111.7 ft. RFJ - Roots Fine Joint, from 07 to 12 o'clock, within 8 inches of joint: YES146.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES154.3 ft. RFJ - Roots Fine Joint, from 12 to 04 o'clock, within 8 inches of joint: YES157.8 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"175.7 ft. RFJ - Roots Fine Joint, from 07 to 10 o'clock, within 8 inches of joint: YES190.8 ft. RFJ - Roots Fine Joint, from 07 to 11 o'clock, within 8 inches of joint: YES203.2 ft. RFJ - Roots Fine Joint, from 08 to 11 o'clock, within 8 inches of joint: YES221.4 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish222.5 ft. AMH - Downstream Manhole, Survey Ends - 18 0076

Observation photos (11)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Missing, from 11 to 01 o'clock, within 8 inches of joint: YES

    7 ft. - Surface Aggregate Missing, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    12.1 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 12 to 03 o'clock,  , within 8 inches of joint: YES

    34.7 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 12 to 03 o'clock, , within 8 inches of joint: YES

  • Infiltration Dripper, from 11 to 01 o'clock, within 8 inches of joint: YES

    61.5 ft. - Infiltration Dripper, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 07 to 11 o'clock, within 8 inches of joint: YES

    82.8 ft. - Roots Fine Joint, from 07 to 11 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 07 to 12 o'clock, within 8 inches of joint: YES

    111.7 ft. - Roots Fine Joint, from 07 to 12 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 12 to 04 o'clock, within 8 inches of joint: YES

    154.3 ft. - Roots Fine Joint, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 07 to 10 o'clock, within 8 inches of joint: YES

    175.7 ft. - Roots Fine Joint, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 07 to 11 o'clock, within 8 inches of joint: YES

    190.8 ft. - Roots Fine Joint, from 07 to 11 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 11 o'clock, within 8 inches of joint: YES

    203.2 ft. - Roots Fine Joint, from 08 to 11 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
154.3RFJ
222.5AMH18 0076
190.8RFJ
12.1SAM
111.7RFJ
3SAP
157.8TFA
203.2RFJ
34.7DAE
0AMH18 0425
175.7RFJ
61.5ID
7SAM
146.7DAE
0MWM
0MWL
221.4SAM
12.1SAP
82.8RFJ

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2018-07-24T01:55:18-07:00
documentation
PROPIPE
is_lateral_inspection
false