Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 30, 2017, 11:39 AM
Date
11/30/2017
W/O
673962
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00042
PipeID
P10281
Time
3:39 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5233
Sewer Name
F JOINT OUTFALL F - UNIT 6
City
NORWALK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
34
Purpose
Routine Assessment
Project
WO_673962_TV02160_DEC2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
F 0145
Downstream MH
F 0146
Dir. of Survey
Upstream
Length Surveyed
186.6 ft.
Total Length
186.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole F 0145 to F 0146
MH: F 0145MH: F 0146upstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Ends - F 01462.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish10.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"65.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"114.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"160.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"184.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start186.6 ft. AMH - Downstream Manhole, Survey Begins - F 0145186.6 ft. MWL - Water Level, 15 %of cross sectional area186.6 ft. MWM - Water Mark, 25 %of cross sectional area

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
186.6MGOCOCKROACHES IN MANHOLE
0AMHF 0145
184.1DAGS
71.8TFC
25.8TFC
2DAGS
176.3TF
0MWL
121.4TFC
186.6AMHF 0146
0MWM

Properties (6)

additional_info
SC346404
custom_field_two
4
customer
LACSD
datetime
2017-11-30T03:39:17-08:00
documentation
PRO PIPE
is_lateral_inspection
false