Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 30, 2017, 10:23 AM
Date
11/30/2017
W/O
673962
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00042
PipeID
P10277
Time
2:23 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5233
Sewer Name
F JOINT OUTFALL F - UNIT 6
City
NORWALK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
34
Purpose
Routine Assessment
Project
WO_673962_TV02160_DEC2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
F 0143
Downstream MH
F 0144
Dir. of Survey
Upstream
Length Surveyed
329.2 ft.
Total Length
329.2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2L00
O&M Rating
130
Overall Index
2
Overall Quick
Overall Rating
130
Pipe schematic from manhole F 0143 to F 0144
MH: F 0143MH: F 0144upstream0 ft. AMH - Upstream Manhole, Survey Ends - F 01440 ft. MGO - General Observation - COCKROACHES IN MANHOLE1.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish53.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"101.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"149.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"200.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"257.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"272.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"327.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start329.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE329.2 ft. MWM - Water Mark, 30 %of cross sectional area329.2 ft. MWL - Water Level, 20 %of cross sectional area329.2 ft. AMH - Downstream Manhole, Survey Begins - F 0143

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
128.6TFC
180TFC
327.6DAGS
0MGOCOCKROACHES IN MANHOLE
228.1TFC
71.5TFC
57TFC
329.2AMHF 0144
2DAGS
0MWM
276.1TFC
329.2MGOCOCKROACHES IN MANHOLE
0MWL
0AMHF 0143

Properties (6)

additional_info
SC346404
custom_field_two
4
customer
LACSD
datetime
2017-11-30T02:23:36-08:00
documentation
PRO PIPE
is_lateral_inspection
false