- Date
- 11/30/2017
- W/O
- 673962
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00042
- PipeID
- P10273
- Time
- 1:49 AM
- Certificate
- U-111-11880
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K5233
- Sewer Name
- F JOINT OUTFALL F - UNIT 6
- City
- NORWALK
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 02
- Page No.
- 34
- Purpose
- Routine Assessment
- Project
- WO_673962_TV02160_DEC2017
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 15 in.
- Width
- 15 in.
- Upstream MH
- F 0140
- Downstream MH
- F 0139
- Dir. of Survey
- Downstream
- Length Surveyed
- 238.2 ft.
- Total Length
- 238.2 ft.
- Structural Index
- 2
- Structural Quick
- 2100
- Structural Rating
- 2
- O&M Index
- 2
- O&M Quick
- 2H00
- O&M Rating
- 94
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 96
Pipe schematic from manhole F 0140 to F 0139 Observation photos (4)

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

238.2 ft. - Drop Connection, Survey Ends - F 0139

238.2 ft. - Tap Factory Made Active, at 06 o'clock, -, within 8 inches of joint: YES, 15" - DROP CONNECTION

238.2 ft. - Crack Spiral, from 12 to 12 o'clock, within 8 inches of joint: YES