Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 8, 2019, 06:42 PM
  • 05 1281_05 1280_882019_115223.mp4

Date
08/08/2019
W/O
0786149
Weather
Dry
Operator/Surveyor
SHADLER
Sewer ID
Z00518
PipeID
P06495
Time
11:42 AM
Certificate
U-415-06024035
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G8048 / G8049
Sewer Name
05 SO HAWTHORNE-WARFIELD AV EXT TR, SECT 4
City
HAWTHORNE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
19
Purpose
Capital Improvement Program Assesment
Project
20190808KS_SO_HAWTHORNE_WARFIELD_AVE_EXT_TRUNK_SECT_4
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
05 1281
Downstream MH
05 1280
Dir. of Survey
Downstream
Length Surveyed
340.6 ft.
Total Length
340.6 ft.
Structural Index
2
Structural Quick
2111
Structural Rating
3
O&M Index
2
O&M Quick
3111
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 05 1281 to 05 1280
MH: 05 1281MH: 05 1280downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. AMH - Upstream Manhole, Survey Begins - 11:51 AM0 ft. MGO - General Observation - DROP CONNECTION @ U/S MH @ 3 O'CLOCK0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start16.7 ft. MGP - General Photograph58.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"62.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4" - Open153.7 ft. CC - Crack Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES263.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"267.2 ft. TBD - Tap Break-In Defective, at 02 o'clock, -, , within 8 inches of joint: NO, 4" - Active, VOID & SOIL267.2 ft. MGP - General Photograph267.2 ft. MGP - General Photograph340.6 ft. MGO - General Observation - DROPPED CONNECTIONS @ D/S MH 9 & 3 o'clock340.6 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active340.6 ft. VC - Vermin Cockroach, within 8 inches of joint: YES - THROUGHOUT REACH340.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish340.6 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active340.6 ft. MGO - General Observation - Grease Throughout The Reach (5%)340.6 ft. AMH - Downstream Manhole, Survey Ends - 12:54 PM

Observation photos (5)

  • General Photograph

    16.7 ft. - General Photograph

  • Crack Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES

    153.7 ft. - Crack Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Tap Break-In Defective, at 02 o'clock, -,  , within 8 inches of joint: NO, 4" - Active, VOID & SOIL

    267.2 ft. - Tap Break-In Defective, at 02 o'clock, -, , within 8 inches of joint: NO, 4" - Active, VOID & SOIL

  • General Photograph

    267.2 ft. - General Photograph

  • General Photograph

    267.2 ft. - General Photograph

Observations (22)

DistanceCodeObservation
0MWM
62.6TFOpen
267.2TBDActive, VOID & SOIL
267.2MGP
0MWL
267.2MGP
0MGOConn. @ Mh, 3 O' Clock. Active
340.6MGODROPPED CONNECTIONS @ D/S MH 9 & 3 o'clock
340.6MGOConn. @ Mh, 9 O' Clock. Active
0AMH11:51 AM
263.2TFC
340.6VCTHROUGHOUT REACH
16.7MGP
340.6SSS
153.7CC
2SSS
340.6MGOConn. @ Mh, 3 O' Clock. Active
0MGODROP CONNECTION @ U/S MH @ 3 O'CLOCK
340.6MGOGrease Throughout The Reach (5%)
58.9TFC
340.6AMH12:54 PM
0MGOConn. @ Mh, 9 O' Clock. Active

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-08-08T11:42:32-07:00
documentation
SHADLER, FRANKLIN, CASTILLO
is_lateral_inspection
false