Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 8, 2019, 05:33 PM
  • 05 1282_05 1281_882019_105205.mp4

Date
08/08/2019
W/O
0786149
Weather
Dry
Operator/Surveyor
SHADLER
Sewer ID
Z00518
PipeID
P06496
Time
10:33 AM
Certificate
U-415-06024035
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G8048
Sewer Name
05 SO HAWTHORNE-WARFIELD AV EXT TR, SECT 4
City
HAWTHORNE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
19
Purpose
Capital Improvement Program Assesment
Project
20190808KS_SO_HAWTHORNE_WARFIELD_AVE_EXT_TRUNK_SECT_4
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
05 1282
Downstream MH
05 1281
Dir. of Survey
Downstream
Length Surveyed
339.5 ft.
Total Length
339.5 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
2111
O&M Rating
3
Overall Index
2
Overall Quick
Overall Rating
8
Pipe schematic from manhole 05 1282 to 05 1281
MH: 05 1282MH: 05 1281downstream0 ft. AMH - Upstream Manhole, Survey Begins - 10:48 AM0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNS. @ U/S MH @ 9 & 3 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN U/S MH0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start47.7 ft. MGP - General Photograph65.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"69.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"176.7 ft. MGP - General Photograph179.9 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 4" - OPEN241.1 ft. MGP - General Photograph266.4 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 4", 4" - Open270.2 ft. TFD - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: NO, 4" - Capped335.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish335.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish339.5 ft. AMH - Downstream Manhole, Survey Ends - 11:41 AM339.5 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active339.5 ft. VC - Vermin Cockroach, within 8 inches of joint: YES339.5 ft. MGO - General Observation - Grease Throughout The Reach (5%)339.5 ft. MGO - General Observation - DROP CONNECTION @ 3 O'CLOCK @ D/S MH339.5 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active

Observation photos (4)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    47.7 ft. - General Photograph

  • General Photograph

    176.7 ft. - General Photograph

  • General Photograph

    241.1 ft. - General Photograph

Observations (23)

DistanceCodeObservation
2SSS
339.5AMH11:41 AM
339.5MGOConn. @ Mh, 9 O' Clock. Active
266.4TFOpen
65.4TFC
176.7MGP
339.5VC
47.7MGP
339.5MGOGrease Throughout The Reach (5%)
2CM
0AMH10:48 AM
0MWM
0MGOACTIVE CONNS. @ U/S MH @ 9 & 3 O'CLOCK
241.1MGP
339.5MGODROP CONNECTION @ 3 O'CLOCK @ D/S MH
179.9TBOPEN
270.2TFDCapped
0MGOCOCKROACHES IN U/S MH
69.4TF
335.9CM
0MWL
339.5MGOConn. @ Mh, 3 O' Clock. Active
335.9SSS

Properties (4)

customer
LACSD
datetime
2019-08-08T10:33:35-07:00
documentation
SHADLER, FRANKLIN, CASTILLO
is_lateral_inspection
false