Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 12, 2019, 11:27 AM
  • Section#3_E 0121_E 0120__8122019__I0213.mp4

Date
08/12/2019
W/O
0784628
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00032
PipeID
P11347
Time
4:27 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0213
Sewer Name
E JOINT OUTFALL E - UNIT 5
City
WILLBROOK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Routine Assessment
Project
20190812MDM_JOINT_OUTFALL_E_UNIT_5
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Upstream MH
E 0121
Downstream MH
E 0120
Dir. of Survey
Downstream
Length Surveyed
491.6 ft.
Total Length
491.6 ft.
Structural Index
2
Structural Quick
312S
Structural Rating
205
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
205
Pipe schematic from manhole E 0121 to E 0120
MH: E 0121MH: E 0120downstream0 ft. AMH - Upstream Manhole, Survey Begins - 4:30AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE2 ft. MGO - General Observation - 95% MAG COAT START21.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE71.1 ft. SSS - Surface Spalling, from 08 to 12 o'clock, within 8 inches of joint: YES - PEELING CONCRETE73.5 ft. SAV - Surface Aggregate Visible, from 08 to 12 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC297.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE UNDER MAG COAT491.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE UNDER MAG COAT491.1 ft. MGO - General Observation - 95% MAG COAT FINISH491.6 ft. AMH - Downstream Manhole, Survey Ends - 5:05AM

Observation photos (6)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • General Observation - 95% MAG COAT START

    2 ft. - General Observation - 95% MAG COAT START

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

    21.5 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

  • Surface Spalling, from 08 to 12 o'clock, within 8 inches of joint: YES - PEELING CONCRETE

    71.1 ft. - Surface Spalling, from 08 to 12 o'clock, within 8 inches of joint: YES - PEELING CONCRETE

  • Surface Aggregate Visible, from 08 to 12 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

    73.5 ft. - Surface Aggregate Visible, from 08 to 12 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE UNDER MAG COAT

    297.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE UNDER MAG COAT

Observations (12)

DistanceCodeObservation
491.1SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
71.1SSSPEELING CONCRETE
21.5SSSBLISTERING CONCRETE
0AMH4:30AM
491.1MGO95% MAG COAT FINISH
2SSSBLISTERING PEELING CONCRETE
491.6AMH5:05AM
0MWL
73.5SAVSEVERE AGG SPORATIC
297.9SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
0MWM
2MGO95% MAG COAT START

Properties (6)

custom_field_three
SEVERE AGG SPORATIC-PEELING CONCRETE-95% MAG COAT
custom_field_two
4
customer
LACSD
datetime
2019-08-12T04:27:01-07:00
documentation
MARTIN,REVELES,BRAR
is_lateral_inspection
false