Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 9, 2019, 06:38 PM
  • 05 0468_05 0467_892019_124823.mp4

Date
08/09/2019
W/O
0786503
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00526
PipeID
P05683
Time
11:38 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G8051
Sewer Name
05 STRAWBERRY AVENUE TRUNK
City
HAWTHORNE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
20190809DF_STRAWBERRY_AVENUE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
05 0468
Downstream MH
05 0467
Dir. of Survey
Downstream
Length Surveyed
289 ft.
Total Length
289 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 05 0468 to 05 0467
MH: 05 0468MH: 05 0467downstream0 ft. AMH - Upstream Manhole, Survey Begins - 12:47 PM0.1 ft. MGO - General Observation - ROACHES @ MH0.1 ft. MWM - Water Mark, 15 %of cross sectional area0.1 ft. MWL - Water Level, 10 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start29.2 ft. MGP - General Photograph38.3 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 4"41.1 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: YES, 4"89.5 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 4" - Open91.9 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4"138 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4" - Open145.5 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 4" - Open153.1 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: YES, 4"155.8 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 4" - Open230.1 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: YES, 4"243.1 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 4" - Open261.2 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 4" - Open263.7 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4"287.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish287.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish289 ft. MGO - General Observation - GREASE THROUGHOUT THE REACH (5%)289 ft. MGO - General Observation - ROACHES @ MH289 ft. AMH - Downstream Manhole, Survey Ends - 1:08 PM

Observation photos (3)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    29.2 ft. - General Photograph

Observations (24)

DistanceCodeObservation
89.5TFOpen
287.1SSS
41.1TFA
2SSS
29.2MGP
289MGOGREASE THROUGHOUT THE REACH (5%)
230.1TFA
0AMH12:47 PM
0.1MGOROACHES @ MH
2CM
0.1MWM
153.1TFA
263.7TF
243.1TFOpen
261.2TFOpen
155.8TFOpen
38.3TF
91.9TF
0.1MWL
138TFOpen
287.1CM
289MGOROACHES @ MH
145.5TFOpen
289AMH1:08 PM

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-08-09T11:38:38-07:00
documentation
FRANKLIN, CASTILLO, RUVALCABA
is_lateral_inspection
false