Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 9, 2019, 07:46 AM
  • 29 0054_29 0053 _01092019_000323.mp4

Date
01/08/2019
W/O
740646
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00020
PipeID
P23834
Time
11:46 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6296
Sewer Name
29 EASTSIDE INTERCEPTOR TRUNK
City
LONG BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
16
Purpose
Routine Assessment
Project
RFIR_WO_740646_TV29114_DEC2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
29 0054
Downstream MH
29 0053
Dir. of Survey
Downstream
Length Surveyed
371.2 ft.
Total Length
371.2 ft.
Structural Index
5
Structural Quick
5141
Structural Rating
9
O&M Index
2
O&M Quick
2N00
O&M Rating
148
Overall Index
2
Overall Quick
Overall Rating
157
Pipe schematic from manhole 29 0054 to 29 0053
MH: 29 0054MH: 29 0053downstream0 ft. AMH - Upstream Manhole, Survey Begins - 29 00540 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start343 ft. B - Broken, from 12 to 03 o'clock, within 8 inches of joint: YES343.7 ft. FM - Fracture Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES369 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish369.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish371.2 ft. AMH - Downstream Manhole, Survey Ends - 29 0053

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

    343.7 ft. - Fracture Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

Observations (10)

DistanceCodeObservation
0AMH29 0054
371.2AMH29 0053
343B
2DAE
369DAE
0MWM
369.6DAGS
343.7FM
0MWL
2DAGS

Properties (6)

additional_info
SC365662
custom_field_two
3
customer
LACSD
datetime
2019-01-08T23:46:37-08:00
documentation
PRO PIPE
is_lateral_inspection
false