Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 26, 2019, 08:17 AM
  • E 0201_E 0200_02262019_013846.mp4

Date
02/26/2019
W/O
751206
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00972
PipeID
P24782
Time
12:17 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6455
Sewer Name
E JOINT OUTFALL E - UNIT 4 RELIEF
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
WO_751206_TV01092_FEB2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
E 0201
Downstream MH
E 0200
Dir. of Survey
Downstream
Length Surveyed
651.5 ft.
Total Length
651.5 ft.
Structural Index
3
Structural Quick
4122
Structural Rating
8
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
11
Pipe schematic from manhole E 0201 to E 0200
MH: E 0201MH: E 0200downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - E 02010 ft. MWL - Water Level, 35 %of cross sectional area300.7 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES521.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES626.7 ft. RMJ - Roots Medium Joint, from 09 to 03 o'clock, 10 %, within 8 inches of joint: YESR645.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES651.5 ft. AMH - Downstream Manhole, Survey Ends - E 0200

Observation photos (4)

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    300.7 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    521.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Roots Medium Joint, from 09 to 03 o'clock, 10 %, within 8 inches of joint: YESR

    626.7 ft. - Roots Medium Joint, from 09 to 03 o'clock, 10 %, within 8 inches of joint: YESR

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    645.8 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (8)

DistanceCodeObservation
0MWM
0AMHE 0201
626.7RMJ
651.5AMHE 0200
645.8FM
300.7CL
521.4CL
0MWL

Properties (6)

custom_field_two
3
customer
LACSD
datetime
2019-02-26T00:17:40-08:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
37770