Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 30, 2019, 09:58 AM
  • Section#2_16 0280_18 0279__7302019__I0197R.mp4

Date
07/30/2019
W/O
#
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00654
PipeID
P13328
Time
2:58 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0197R
Sewer Name
16 CHAPEL AVENUE TRUNK, SECTION 3
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
17
Purpose
Maintenance Related
Project
20190730MDM_CHAPEL_AVENUE_TRUNK_SECTION_3
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
16 0280
Downstream MH
18 0279
Dir. of Survey
Downstream
Length Surveyed
280 ft.
Total Length
280 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
4
Pipe schematic from manhole 16 0280 to 18 0279
MH: 16 0280MH: 18 0279downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:30AM0 ft. MWL - Water Level, 10 %of cross sectional area132.9 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6", 6" - OPEN204.9 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN280 ft. AMH - Downstream Manhole, Survey Ends - 3:45AM

Observations (6)

DistanceCodeObservation
280AMH3:45AM
0MWM
0AMH3:30AM
132.9TBOPEN
204.9TBOPEN
0MWL

Properties (6)

additional_info
POST ROOT EVALUATION ONLY
customer
LACSD
datetime
2019-07-30T02:58:22-07:00
documentation
MARTIN,OLIVER 111,SHADLER
is_lateral_inspection
false
lining
CIPP