Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 21, 2019, 08:38 AM
  • 15_1_1_21062019_015109.mp4

Date
06/21/2019
W/O
766407
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00349
PipeID
P02984
Time
1:38 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6572
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
BELL GARDENS
Loc. details
Railway
Location Code
L
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
20
Purpose
Routine Assessment
Project
WO_766407_TV02220_MAY2019
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
63 in.
Width
63 in.
Upstream MH
02 1413
Downstream MH
02 1412
Dir. of Survey
Downstream
Length Surveyed
2.5 ft.
Total Length
2.5 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
4
Overall Quick
Overall Rating
14
Pipe schematic from manhole 02 1413 to 02 1412
MH: 02 1413MH: 02 1412downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 14130 ft. MWM - Water Mark, 70 %of cross sectional area0 ft. MWL - Water Level, 55 %of cross sectional area2.5 ft. MSA - Survey Abandoned - VIEW OF THE DOWNLEG PIPE FROM THE U/S SIDE OF THE2.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: NO2.5 ft. SAP - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: NO2.5 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock,  , within 8 inches of joint: NO

    2.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: NO

  • Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: NO

    2.5 ft. - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO

    2.5 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO

Observations (7)

DistanceCodeObservation
0AMH02 1413
2.5MSAVIEW OF THE DOWNLEG PIPE FROM THE U/S SIDE OF THE
0MWM
2.5DAGS
2.5SAP
0MWL
2.5SRV

Properties (6)

additional_info
SC377697
custom_field_two
2
customer
LACSD
datetime
2019-06-21T01:38:29-07:00
documentation
PROPIPE
is_lateral_inspection
false