Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 21, 2019, 07:21 AM
  • 1_1_1_21062019_003651.mp4

Date
06/21/2019
W/O
766407
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00349
PipeID
P02962
Time
12:21 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6572
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
BELL GARDENS
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
26
Purpose
Routine Assessment
Project
WO_766407_TV02220_MAY2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Width
57 in.
Upstream MH
02 1391
Downstream MH
02 1390
Dir. of Survey
Downstream
Length Surveyed
243.4 ft.
Total Length
243.7 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
144
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
144
Pipe schematic from manhole 02 1391 to 02 1390
MH: 02 1391MH: 02 1390downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 13913 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3 ft. MGO - General Observation - MAG COAT THROUGHOUT PIPE243.4 ft. MSA - Survey Abandoned - CABLE MAXED OUT243.4 ft. MGO - General Observation - MH VISIBLE243.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0MWM
0MWL
243.4MSACABLE MAXED OUT
3SAP
3MGOMAG COAT THROUGHOUT PIPE
0AMH02 1391
243.4MGOMH VISIBLE
243.4SAP

Properties (6)

additional_info
SC377697
custom_field_two
3
customer
LACSD
datetime
2019-06-21T00:21:12-07:00
documentation
PROPIPE
is_lateral_inspection
false