Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 19, 2019, 10:00 AM
  • 11_1_1_19062019_031400.mp4

Date
06/19/2019
W/O
766407
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00349
PipeID
P02972
Time
3:00 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6570
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
BELL GARDENS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
23
Purpose
Routine Assessment
Project
WO_766407_TV02220_MAY2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
02 1401
Downstream MH
02 1400
Dir. of Survey
Downstream
Length Surveyed
160.8 ft.
Total Length
160.8 ft.
Structural Index
4
Structural Quick
5E3E
Structural Rating
250
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
250
Pipe schematic from manhole 02 1401 to 02 1400
MH: 02 1401MH: 02 1400downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 14016.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.5 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start122 ft. SRC - Surface Reinforcement Corroded, from 08 to 12 o'clock, within 8 inches of joint: NO153.5 ft. SRC - Surface Reinforcement Corroded, from 08 to 12 o'clock, within 8 inches of joint: NO157.3 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish157.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish160.8 ft. MGO - General Observation - CONNECTION IN MH AT 9 AND 3 OCLOCK160.8 ft. AMH - Downstream Manhole, Survey Ends - 02 1400

Observation photos (4)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.4 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    6.5 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Corroded, from 08 to 12 o'clock, within 8 inches of joint: NO

    122 ft. - Surface Reinforcement Corroded, from 08 to 12 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Corroded, from 08 to 12 o'clock, within 8 inches of joint: NO

    153.5 ft. - Surface Reinforcement Corroded, from 08 to 12 o'clock, within 8 inches of joint: NO

Observations (11)

DistanceCodeObservation
0MWL
157.3SRV
6.4SAP
160.8MGOCONNECTION IN MH AT 9 AND 3 OCLOCK
153.5SRC
160.8AMH02 1400
122SRC
6.5SRV
0MWM
157.3SAP
0AMH02 1401

Properties (6)

additional_info
SC377695
custom_field_two
2
customer
LACSD
datetime
2019-06-19T03:00:03-07:00
documentation
PROPIPE
is_lateral_inspection
false