Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 12, 2019, 06:15 AM
  • 9_1_3_11042019_232243.mp4

Date
04/11/2019
W/O
761426
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00141
PipeID
P09842
Time
11:15 PM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5927
Sewer Name
C JOINT OUTFALL C - UNIT 8C
City
LAKEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
06
Purpose
Routine Assessment
Project
WO_761426_TV19012_APR2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
19 ELAINE
Downstream MH
C 0378
Dir. of Survey
Downstream
Length Surveyed
38.2 ft.
Total Length
38.2 ft.
Structural Index
2
Structural Quick
3127
Structural Rating
17
O&M Index
3
O&M Quick
4122
O&M Rating
8
Overall Index
2
Overall Quick
Overall Rating
25
Pipe schematic from manhole 19 ELAINE to C 0378
MH: 19 ELAINEMH: C 0378downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 19 ELAINE (C JOINT)1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2.9 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start - MAG COAT2.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.9 ft. LL - Alignment Left, 15 %36.5 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish36.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish38 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish38.2 ft. AMH - Downstream Manhole, Survey Ends - C 0378

Observation photos (3)

  • Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start - MAG COAT

    2.9 ft. - Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start - MAG COAT

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.9 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Alignment Left, 15 %

    2.9 ft. - Alignment Left, 15 %

Observations (11)

DistanceCodeObservation
38SSS
0MWM
36.5DAZ
2.9DAZMAG COAT
0MWL
36.5SAP
2.9SAP
0AMH19 ELAINE (C JOINT)
38.2AMHC 0378
1SSS
2.9LL

Properties (6)

custom_field_two
3
customer
LACSD
datetime
2019-04-11T23:15:08-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
26760