Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 22, 2019, 04:11 PM
  • 16 0572_16 0571_7222019_093743.mp4

Date
07/22/2019
W/O
0782150
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00659
PipeID
P13623
Time
9:11 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Jetting
Media Label
G8034
Sewer Name
16 LAMANDA PARK TRUNK
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
11
Purpose
Maintenance Related
Project
20190722DF_LAMANDA_PARK_TRUNK
Material
Reinforced Concrete Pipe
Shape
Circular
Height
22 in.
Upstream MH
16 0572
Downstream MH
16 0571
Dir. of Survey
Downstream
Length Surveyed
257 ft.
Total Length
257 ft.
Structural Index
4
Structural Quick
5232
Structural Rating
18
O&M Index
2
O&M Quick
2411
O&M Rating
9
Overall Index
3
Overall Quick
Overall Rating
27
Pipe schematic from manhole 16 0572 to 16 0571
MH: 16 0572MH: 16 0571downstream0 ft. AMH - Upstream Manhole, Survey Begins - 9:13 AM0.1 ft. MWM - Water Mark, 20 %of cross sectional area0.1 ft. MWL - Water Level, 15 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start14.3 ft. MGP - General Photograph - RAT/VERMIN20.9 ft. MGP - General Photograph - RAT/VERMIN22.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4" - Unkown27.2 ft. MGP - General Photograph38.3 ft. MGP - General Photograph38.3 ft. RFL - Roots Fine Lateral, at 11 o'clock - 5%38.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4"54.6 ft. MGP - General Photograph71.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4"91.4 ft. RTJ - Roots Tap Joint, at 11 o'clock, 5 %, within 8 inches of joint: YESR91.4 ft. MGP - General Photograph91.4 ft. TFD - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: YES, 4" - 5% ROOTS115.6 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 4" - Open135.7 ft. TFD - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: YES, 4" - 25% ROOTS/LATERAL135.7 ft. MGP - General Photograph163.9 ft. TFD - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: YES, 4" - 10% ROOTS/LATERAL184.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4" - 5% ROOTS216.7 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 4"236.1 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 4"256.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish256.8 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish256.8 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish256.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish256.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish257 ft. MGO - General Observation - Grease Throughout The Reach (5%)257 ft. AMH - Downstream Manhole, Survey Ends - 10:05 AM

Observation photos (19)

  • Upstream Manhole, Survey Begins - 9:13 AM

    0 ft. - Upstream Manhole, Survey Begins - 9:13 AM

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph - RAT/VERMIN

    14.3 ft. - General Photograph - RAT/VERMIN

  • General Photograph - RAT/VERMIN

    20.9 ft. - General Photograph - RAT/VERMIN

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4" - Unkown

    22.1 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4" - Unkown

  • General Photograph

    27.2 ft. - General Photograph

  • General Photograph

    38.3 ft. - General Photograph

  • Roots Fine Lateral, at 11 o'clock - 5%

    38.3 ft. - Roots Fine Lateral, at 11 o'clock - 5%

  • General Photograph

    54.6 ft. - General Photograph

  • Roots Tap Joint, at 11 o'clock, 5 %, within 8 inches of joint: YESR

    91.4 ft. - Roots Tap Joint, at 11 o'clock, 5 %, within 8 inches of joint: YESR

  • General Photograph

    91.4 ft. - General Photograph

  • Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: YES, 4" - 5% ROOTS

    91.4 ft. - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: YES, 4" - 5% ROOTS

  • Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: YES, 4" - 25% ROOTS/LATERAL

    135.7 ft. - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: YES, 4" - 25% ROOTS/LATERAL

  • General Photograph

    135.7 ft. - General Photograph

  • Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: YES, 4" - 10% ROOTS/LATERAL

    163.9 ft. - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: YES, 4" - 10% ROOTS/LATERAL

Observations (34)

DistanceCodeObservation
0AMH9:13 AM
256.8SAP
0.1MWM
257MGOGrease Throughout The Reach (5%)
115.6TFOpen
256.8SRC
2SSS
22.1TFUnkown
236.1TFA
2SRV
163.9TFD10% ROOTS/LATERAL
38.3MGP
38.3RFL5%
91.4RTJ
0.1MWL
71.5TFC
54.6MGP
257AMH10:05 AM
27.2MGP
256.8SRV
256.8SSS
2SAV
256.8SAV
20.9MGPRAT/VERMIN
135.7TFD25% ROOTS/LATERAL
38.3TFC
91.4MGP
184.9TFC5% ROOTS
216.7TFA
91.4TFD5% ROOTS
135.7MGP
14.3MGPRAT/VERMIN
2SAP
2SRC

Properties (7)

additional_info
ROOT EVALUATION ONLY
custom_field_three
AGGREGATE PROJECTING, REINFORCEMENT CORRODED
custom_field_two
2
customer
LACSD
datetime
2019-07-22T09:11:28-07:00
documentation
FRANKLIN, CASTILLO, RUVALCABA, IGNACIO
is_lateral_inspection
false