Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 18, 2018, 08:05 AM
  • 02 1147_02 1146_10182018_022518.mp4

Date
10/18/2018
W/O
0734330
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00351
PipeID
P02931
Time
1:05 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Heavy Cleaning
Media Label
H1017
Sewer Name
02 GARFIELD AVENUE EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
13
Purpose
Maintenance Related
Project
20181018MDM_GARFIELD_AVENUE_EXTENSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
02 1147
Downstream MH
02 1146
Dir. of Survey
Downstream
Length Surveyed
291.5 ft.
Total Length
291.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
4
O&M Quick
4231
O&M Rating
11
Overall Index
4
Overall Quick
Overall Rating
11
Pipe schematic from manhole 02 1147 to 02 1146
MH: 02 1147MH: 02 1146downstream0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN0 ft. MWL - Water Level, 50 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:25AM3 ft. DAGS - Deposits Attached Grease, 20 %of cross sectional area, from 10 to 02 o'clock, , within 8 inches of joint: NO45 ft. MWL - Water Level, 10 %of cross sectional area45 ft. MWM - Water Mark, 60 %of cross sectional area125.7 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open162.2 ft. MGO - General Observation - 10" VCP & CIPP291.1 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active291.5 ft. AMH - Downstream Manhole, Survey Ends - 2:55AM

Observation photos (1)

  • General Observation - 10" VCP & CIPP

    162.2 ft. - General Observation - 10" VCP & CIPP

Observations (12)

DistanceCodeObservation
0MGOConn. @ Mh, 9 O' Clock. Active
0MGOConn. @ Mh, 3 O' Clock. OPEN
3DAGS
45MWL
0MWL
291.5AMH2:55AM
0MWM
162.2MGO10" VCP & CIPP
125.7TBOpen
45MWM
0AMH2:25AM
291.1MGOConn. @ Mh, 3 O' Clock. Active

Properties (6)

additional_info
LOOKING FOR MAJOR PIPE DAMAGE
customer
LACSD
datetime
2018-10-18T01:05:18-07:00
documentation
MARTIN,REVELES,OLIVER 111,BRAR
is_lateral_inspection
false
lining
CIPP