Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 17, 2018, 11:44 AM
  • 01 0736_G 0120_10172018_044957.mp4

Date
10/17/2018
W/O
0734330
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00205
PipeID
P01643
Time
4:44 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1015
Sewer Name
01 COMPTON DISPOSAL TRUNK
City
COMPTON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
20
Purpose
Capital Improvement Program Assesment
Project
20181015MDM_COMPTON_DISPOSAL_TRUNK
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
01 0736
Downstream MH
G 0120
Dir. of Survey
Downstream
Length Surveyed
260.5 ft.
Total Length
260.5 ft.
Structural Index
4
Structural Quick
5742
Structural Rating
48
O&M Index
3
O&M Quick
4122
O&M Rating
8
Overall Index
4
Overall Quick
Overall Rating
56
Pipe schematic from manhole 01 0736 to G 0120
MH: 01 0736MH: G 0120downstream-0.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Capped0 ft. AMH - Upstream Manhole, Survey Begins - 4:55 AM0 ft. MWM - Water Mark, 70 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. MGO - General Observation - MAG COAT 30% START 10:00 TO 2:002 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BLISTERING CONCRETE8.6 ft. MGO - General Observation - MAG COAT 20% START 10:00 TO 2:0010.5 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR17.8 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG34.4 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR39.8 ft. SRV - Surface Reinforcement Visible, at 10 o'clock, within 8 inches of joint: NO - CIRCUM REBAR45.8 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR74.7 ft. MWL - Water Level, 30 %of cross sectional area74.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR74.7 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start - SLUDGE112.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 10 to 02 o'clock, , within 8 inches of joint: YES, Start137.7 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish - SLUDGE140.5 ft. MGO - General Observation - MAG COAT 70% START203.1 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR234 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR245.8 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR256.1 ft. MGP - General Photograph - SMOOTH CONCRETE OR METAL256.1 ft. H - Hole, at 12 o'clock, within 8 inches of joint: YES - MISSING PIPE=AREA OF SMOOTH CONCRETE 4" X4"259.5 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - BLISTERING CONCRETE259.5 ft. MGO - General Observation - MAG COAT 70% FINISH259.5 ft. MGO - General Observation - Conn. @ Mh, 12 O' Clock. OPEN259.5 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR259.5 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG259.5 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active-LARGE INCOMING259.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 10 to 02 o'clock, , within 8 inches of joint: YES, Finish259.9 ft. AMH - Downstream Manhole, Survey Ends - 5:40AM

Observation photos (16)

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - MAG COAT 30% START 10:00 TO 2:00

    2 ft. - General Observation - MAG COAT 30% START 10:00 TO 2:00

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BLISTERING CONCRETE

    2 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BLISTERING CONCRETE

  • General Observation - MAG COAT 20% START 10:00 TO 2:00

    8.6 ft. - General Observation - MAG COAT 20% START 10:00 TO 2:00

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR

    10.5 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

    17.8 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    34.4 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, at 10 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    39.8 ft. - Surface Reinforcement Visible, at 10 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    45.8 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Deposits Attached Grease, 5 %of cross sectional area, from 10 to 02 o'clock,  , within 8 inches of joint: YES, Start

    112.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 10 to 02 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - MAG COAT 70% START

    140.5 ft. - General Observation - MAG COAT 70% START

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    203.1 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    234 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    245.8 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • General Photograph - SMOOTH CONCRETE OR METAL

    256.1 ft. - General Photograph - SMOOTH CONCRETE OR METAL

  • Hole, at 12 o'clock, within 8 inches of joint: YES - MISSING PIPE=AREA OF SMOOTH CONCRETE 4" X4"

    256.1 ft. - Hole, at 12 o'clock, within 8 inches of joint: YES - MISSING PIPE=AREA OF SMOOTH CONCRETE 4" X4"

Observations (33)

DistanceCodeObservation
2SAMSEVERE AGG
0MGOConn. @ Mh, 3 O' Clock. Capped
259.5SSSBLISTERING CONCRETE
2MGOMAG COAT 30% START 10:00 TO 2:00
39.8SRVCIRCUM REBAR
259.5MGOMAG COAT 70% FINISH
0AMH4:55 AM
0MWM
74.7MWL
259.9AMH5:40AM
74.7SRCCIRCUM REBAR
34.4SRVCIRCUM REBAR
203.1SRCCIRCUM REBAR
259.5MGOConn. @ Mh, 12 O' Clock. OPEN
2SSSBLISTERING CONCRETE
74.7DSZSLUDGE
112.6DAGS
256.1MGPSMOOTH CONCRETE OR METAL
245.8SRCCIRCUM REBAR
0MWL
17.8SAMSEVERE AGG
137.7DSZSLUDGE
256.1HMISSING PIPE=AREA OF SMOOTH CONCRETE 4" X4"
259.5SRCCIRCUM REBAR
45.8SRCCIRCUM REBAR
259.5SAMSEVERE AGG
259.5MGOConn. @ Mh, 9 O' Clock. Active-LARGE INCOMING
10.5SRCCIRCUM REBAR
-0.6SRCCIRCUM REBAR
8.6MGOMAG COAT 20% START 10:00 TO 2:00
234SRCCIRCUM REBAR
140.5MGOMAG COAT 70% START
259.5DAGS

Properties (6)

custom_field_three
CIRCUM REBAR CORRODED--4" X4" HOLE IN PIPE SEALED
custom_field_two
2
customer
LACSD
datetime
2018-10-17T04:44:04-07:00
documentation
MARTIN,REVELES,OLIVER 111,BRAR
is_lateral_inspection
false