Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 21, 2018, 10:37 AM
  • 20 0144_20 0143 _21032018_035613.mp4

Date
03/21/2018
W/O
690447
Weather
Light Rain
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00745
PipeID
P19067
Time
3:37 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5493
Sewer Name
20 TRUNK "D"
City
PALMDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 20
Page No.
06
Purpose
Routine Assessment
Project
WO_690447_TV20029_MAR2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
20 0143
Downstream MH
20 0144
Dir. of Survey
Upstream
Length Surveyed
382 ft.
Total Length
382 ft.
Structural Index
3
Structural Quick
3N00
Structural Rating
228
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
232
Pipe schematic from manhole 20 0143 to 20 0144
MH: 20 0143MH: 20 0144upstream0 ft. AMH - Upstream Manhole, Survey Ends - 20 01441.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish7.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"30.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"54.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4", 4"82.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"107 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"131.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"155.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"183.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"192.4 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 4"208 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"232.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"256.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"284.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"309.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"333 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"357.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"380 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start382 ft. MWM - Water Mark, 50 %of cross sectional area382 ft. AMH - Downstream Manhole, Survey Begins - 20 0143382 ft. MWL - Water Level, 20 %of cross sectional area

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (22)

DistanceCodeObservation
174TFC
0MWM
299.2TFC
0AMH20 0143
327.1TFC
149.8TFC
189.6TB
125.6TF
72.8TF
382AMH20 0144
226.6TFC
275TF
380.1SAP
24.5TF
49TFC
198.1TFC
351.4TFC
374.7TFC
250.8TFC
97.5TFC
0MWL
2SAP

Properties (6)

additional_info
SC358501
custom_field_two
2
customer
LACSD
datetime
2018-03-21T03:37:54-07:00
documentation
PRO PIPE
is_lateral_inspection
false