Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 21, 2016, 09:42 AM
  • 22 0489_22 0488_20160421_040328.mp4

Date
04/21/2016
W/O
563425
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00800
PipeID
P16828
Time
2:42 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K 3187
Sewer Name
22 COVINA CONNECTION EXTENSION TRUNK
City
COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
31
Purpose
Routine Assessment
Project
WO_563425_TV22031_APRIL2016
Sewer Type
GRAVITY
Material
NRCP
Shape
Circular
Height
10 in.
Upstream MH
22 0489
Downstream MH
22 0488
Dir. of Survey
Downstream
Length Surveyed
308.7 ft.
Total Length
308.7 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 22 0489 to 22 0488
MH: 22 0489MH: 22 0488downstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 04890 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. VC - Vermin Cockroach2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start48.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"51.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"96 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"98.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"144.9 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 4"146.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"149.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"194.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"196.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"245.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"247.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"298.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"301.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"306.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish308.7 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK308.7 ft. AMH - Downstream Manhole, Survey Ends - 22 0488

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
298.4TFC
48.5TFC
306.3SAV
96TFC
98.9TFA
194.4TFC
247.8TFC
0AMH22 0489
2SAV
0MWM
51.3TFC
149.6TFC
146.4TFC
301.4TFC
308.7MGOCONNECTION AT THE MH 3 OC'LOCK
308.7AMH22 0488
0MWL
144.9TB
245.1TFC
196.9TFC
0VC

Properties (6)

additional_info
SC226235
custom_field_two
3
customer
LACSD
datetime
2016-04-21T02:42:06-07:00
documentation
PRO PIPE
is_lateral_inspection
false