Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 21, 2016, 07:39 AM
  • 22 0494_22 0493_20160421_015557.mp4

Date
04/21/2016
W/O
563425
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00800
PipeID
P16833
Time
12:39 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K 3187
Sewer Name
22 COVINA CONNECTION EXTENSION TRUNK
City
COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
31
Purpose
Routine Assessment
Project
WO_563425_TV22031_APRIL2016
Sewer Type
GRAVITY
Material
NRCP
Shape
Circular
Height
10 in.
Upstream MH
22 0494
Downstream MH
22 0493
Dir. of Survey
Downstream
Length Surveyed
168.3 ft.
Total Length
168.3 ft.
Structural Index
3
Structural Quick
4134
Structural Rating
16
O&M Index
1
O&M Quick
2114
O&M Rating
6
Overall Index
2
Overall Quick
Overall Rating
22
Pipe schematic from manhole 22 0494 to 22 0493
MH: 22 0494MH: 22 0493downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 04941.8 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start12 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"15 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 4"29 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES40.5 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES40.5 ft. RFJ - Roots Fine Joint, from 08 to 10 o'clock, within 8 inches of joint: YES49.3 ft. RFJ - Roots Fine Joint, from 08 to 10 o'clock, within 8 inches of joint: YES55.8 ft. RFJ - Roots Fine Joint, from 07 to 09 o'clock, within 8 inches of joint: YES59.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"62.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"76 ft. RFJ - Roots Fine Joint, from 07 to 10 o'clock, within 8 inches of joint: YES, Start87 ft. RFJ - Roots Fine Joint, from 07 to 10 o'clock, within 8 inches of joint: YES, Finish100.1 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES110.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"113.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"133.7 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES155.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"158.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"165.3 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish168.3 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK168.3 ft. AMH - Downstream Manhole, Survey Ends - 22 0493

Observation photos (10)

  • Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    1.8 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    15 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    29 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    40.5 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 10 o'clock, within 8 inches of joint: YES

    40.5 ft. - Roots Fine Joint, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 10 o'clock, within 8 inches of joint: YES

    49.3 ft. - Roots Fine Joint, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 07 to 09 o'clock, within 8 inches of joint: YES

    55.8 ft. - Roots Fine Joint, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 07 to 10 o'clock, within 8 inches of joint: YES, Start

    76 ft. - Roots Fine Joint, from 07 to 10 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    100.1 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    133.7 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES

Observations (25)

DistanceCodeObservation
40.5FL
158.6TFC
1.8SAV
0MGOCONNECTION AT THE MH 3 OC'LOCK
15TFD
49.3RFJ
113.6TFC
12TFC
0MWL
168.3MGOCONNECTION AT THE MH 9 OC'LOCK
168.3AMH22 0493
29FM
76RFJ
110.6TFC
59.8TFC
100.1FL
165.3SAV
55.8RFJ
40.5RFJ
87RFJ
0MWM
0AMH22 0494
155.9TFC
133.7FL
62.8TFC

Properties (6)

additional_info
SC226235
custom_field_two
3
customer
LACSD
datetime
2016-04-21T00:39:52-07:00
documentation
PRO PIPE
is_lateral_inspection
false