Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 21, 2016, 07:25 AM
  • 22 0495_22 0494_20160421_013609.mp4

Date
04/21/2016
W/O
563425
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00800
PipeID
P16834
Time
12:25 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K 3187
Sewer Name
22 COVINA CONNECTION EXTENSION TRUNK
City
COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
31
Purpose
Routine Assessment
Project
WO_563425_TV22031_APRIL2016
Sewer Type
GRAVITY
Material
NRCP
Shape
Circular
Height
10 in.
Upstream MH
22 0495
Downstream MH
22 0494
Dir. of Survey
Downstream
Length Surveyed
167.5 ft.
Total Length
167.5 ft.
Structural Index
3
Structural Quick
4132
Structural Rating
10
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 22 0495 to 22 0494
MH: 22 0495MH: 22 0494downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 04952 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start26.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"29.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"58.1 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: NO64.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start77.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"80.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"128.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"131.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"162.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish164.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish167.5 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK167.5 ft. AMH - Downstream Manhole, Survey Ends - 22 0494

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: NO

    58.1 ft. - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: NO

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    64.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
0MWL
64.2FM
29.3TFC
0MWM
164.3SAV
167.5MGOCONNECTION AT THE MH 3 OC'LOCK
167.5AMH22 0494
26.5TFC
128.4TFC
162.2FM
131.6TFC
0AMH22 0495
2SAV
80.5TFC
77.3TFC
58.1FL

Properties (6)

additional_info
SC226235
custom_field_two
3
customer
LACSD
datetime
2016-04-21T00:25:30-07:00
documentation
PRO PIPE
is_lateral_inspection
false