Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 17, 2016, 07:51 AM
  • 03 0366_03 0365_20160517_010100.mp4

Date
05/17/2016
W/O
557879
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00381
PipeID
P05165
Time
12:51 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3378
Sewer Name
03 MARINA RELIEF TRUNK, SECTION 1B
City
LONG BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
24
Purpose
Routine Assessment
Project
WO_557879_TV03013_MARCH2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Lining Method
Segmented Panel
Shape
Circular
Height
27 in.
Upstream MH
03 0366
Downstream MH
03 0365
Dir. of Survey
Downstream
Length Surveyed
321.9 ft.
Total Length
321.9 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 03 0366 to 03 0365
MH: 03 0366MH: 03 0365downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 03 03662.1 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO15.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"95.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"177.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"257.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"308.6 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES321.9 ft. MGO - General Observation - CONNECTION AT MH 9 OCLOCK321.9 ft. AMH - Downstream Manhole, Survey Ends - 03 0365

Observation photos (2)

  • Deposits Settled Other,  10 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: NO

    2.1 ft. - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    308.6 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
95.9TF
15.8TF
2.1DSZ
257.9TF
177.1TF
0MWM
321.9MGOCONNECTION AT MH 9 OCLOCK
0MWL
321.9AMH03 0365
308.6CL
0AMH03 0366

Properties (6)

additional_info
SC300377
custom_field_two
4
customer
LACSD
datetime
2016-05-17T00:51:22-07:00
documentation
PROPIPE
is_lateral_inspection
false