Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 6, 2018, 10:07 AM
  • B 0456_B 0455 _06062018_031455.mp4

Date
06/06/2018
W/O
706794
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00093
PipeID
P08969
Time
3:07 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5689
Sewer Name
B JOINT OUTFALL B - UNIT 5C
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
11
Purpose
Routine Assessment
Project
WO_706794_TV16033_JUN2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
B 0456
Downstream MH
B 0455
Dir. of Survey
Downstream
Length Surveyed
102.3 ft.
Total Length
102.3 ft.
Structural Index
3
Structural Quick
3C00
Structural Rating
60
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
3
Overall Quick
Overall Rating
61
Pipe schematic from manhole B 0456 to B 0455
MH: B 0456MH: B 0455downstream0 ft. AMH - Upstream Manhole, Survey Begins - B 04560 ft. MGO - General Observation - CONNECTION AT MH 5 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area2.1 ft. MGO - General Observation - MAG COAT2.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start18.5 ft. RFJ - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES80.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"102.3 ft. AMH - Downstream Manhole, Survey Ends - B 0455102.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
2.1MGOMAG COAT
0AMHB 0456
0MGOCONNECTION AT MH 5 O'CLOCK
0MWL
18.5RFJ
102.3AMHB 0455
0MWM
2.3SAV
80.2TFC
102.3SAV

Properties (6)

additional_info
SC359348
custom_field_two
3
customer
LACSD
datetime
2018-06-06T03:07:46-07:00
documentation
PROPIPE
is_lateral_inspection
false