Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 6, 2017, 10:32 AM
  • J 0142_J 0141 _06092017_033312.mp4

Date
09/06/2017
W/O
651864
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00052
PipeID
P11375
Time
3:32 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4858
Sewer Name
J JOINT OUTFALL J - UNIT 1A
City
LOMITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
36
Purpose
Routine Assessment
Project
WO_651864_TV05159_AUG2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
J 0142
Downstream MH
J 0141
Dir. of Survey
Downstream
Length Surveyed
316.4 ft.
Total Length
316.4 ft.
Structural Index
3
Structural Quick
413K
Structural Rating
190
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
190
Pipe schematic from manhole J 0142 to J 0141
MH: J 0142MH: J 0141downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - J 01424.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start43.4 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES312.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish316.4 ft. AMH - Downstream Manhole, Survey Ends - J 0141

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    43.4 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (7)

DistanceCodeObservation
0MWL
0MWM
43.4FM
4.8CM
316.4AMHJ 0141
0AMHJ 0142
312.3CM

Properties (6)

additional_info
SC345917
custom_field_two
3
customer
LACSD
datetime
2017-09-06T03:32:47-07:00
documentation
PROPIPE
is_lateral_inspection
false