Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 5, 2018, 07:38 AM
  • 02 0006_02 0005A_05062018_010043.mp4

Date
06/05/2018
W/O
706730
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00234
PipeID
P03032
Time
12:38 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5185
Sewer Name
02 ARTESIA EXTENSION TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
38
Purpose
Routine Assessment
Project
WO_706730_TV02341_JUN2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
02 0006
Downstream MH
02 0005A
Dir. of Survey
Downstream
Length Surveyed
285.2 ft.
Total Length
285.2 ft.
Structural Index
3
Structural Quick
4133
Structural Rating
15
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
19
Pipe schematic from manhole 02 0006 to 02 0005A
MH: 02 0006MH: 02 0005Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 00060 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start7.2 ft. CS - Crack Spiral, from 09 to 03 o'clock, within 8 inches of joint: YES, Start18.9 ft. CS - Crack Spiral, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish19.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start24.8 ft. FS - Fracture Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Start40.5 ft. FS - Fracture Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish45.8 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"47.1 ft. FS - Fracture Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES52.7 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish52.7 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start115.2 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"192.4 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"195.9 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"244.7 ft. TBC - Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"283 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish283 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish285.2 ft. AMH - Downstream Manhole, Survey Ends - 02 0005A

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Spiral, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    7.2 ft. - Crack Spiral, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    19.3 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Fracture Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

    24.8 ft. - Fracture Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

  • Fracture Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES

    47.1 ft. - Fracture Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    52.7 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
0AMH02 0006
47.1FS
285.2AMH02 0005A
18.9CS
192.4TB
40.5FS
244.7TBC
52.7CM
7.2CS
283FM
19.3CM
195.9TBA
0MWL
0MWM
283DAGS
24.8FS
45.8TBA
52.7FM
115.2TBA
3DAGS

Properties (6)

additional_info
SC359507
custom_field_two
1
customer
LACSD
datetime
2018-06-05T00:38:37-07:00
documentation
PROPIPE
is_lateral_inspection
false