Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 1, 2018, 09:58 AM
  • H 0559_H 0558 _01062018_032108.mp4

Date
06/01/2018
W/O
701217
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00186
PipeID
P10983
Time
2:58 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5682
Sewer Name
H JOINT OUTFALL H - UNIT 8C
City
BALDWIN PARK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
24
Purpose
Routine Assessment
Project
WO_701217_TV15170_MAY2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
H 0559
Downstream MH
H 0558
Dir. of Survey
Downstream
Length Surveyed
604.5 ft.
Total Length
604.5 ft.
Structural Index
3
Structural Quick
3W2B
Structural Rating
389
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
389
Pipe schematic from manhole H 0559 to H 0558
MH: H 0559MH: H 0558downstream0 ft. AMH - Upstream Manhole, Survey Begins - H 05590 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start11 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"35.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"58.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"67 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"81.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish114.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"123.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"147.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"168.7 ft. MGO - General Observation - UNMAPPED MH181.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"205.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"237.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"245.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"261.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"293.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"357.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"390.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"446 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"485.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"518.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"558.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"574.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"582.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"599.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish604.5 ft. MGO - General Observation - CAPPED LATERAL 3 O'CLOCK @ MH604.5 ft. AMH - Downstream Manhole, Survey Ends - H 0558

Observation photos (3)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.8 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.8 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - UNMAPPED MH

    168.7 ft. - General Observation - UNMAPPED MH

Observations (32)

DistanceCodeObservation
604.5MGOCAPPED LATERAL 3 O'CLOCK @ MH
168.7MGOUNMAPPED MH
81.5SSS
11TF
0AMHH 0559
293.7TF
181.4TFC
147.1TF
390.1TF
518.3TF
0MGOCONNECTION AT MH 9 O'CLOCK
0MWM
446TF
558.3TF
114.9TF
2.8SAP
0MWL
582.4TF
604.5AMHH 0558
357.8TF
205.9TF
245.7TFC
574.5TF
237.7TF
599.1SAP
67TF
2.8SSS
123.1TF
58.3TFC
35.1TF
485.3TF
261.7TF

Properties (6)

additional_info
SC359340
custom_field_two
3
customer
LACSD
datetime
2018-06-01T02:58:36-07:00
documentation
PROPIPE
is_lateral_inspection
false