Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 20, 2017, 07:30 AM
  • 02 0025_02 0024_7202017_024115.mp4

Date
07/20/2017
W/O
0641143
Weather
Dry
Operator/Surveyor
REVELES
Sewer ID
Z00234
PipeID
P03055
Time
12:30 AM
Certificate
U-11506022630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0596
Sewer Name
02 ARTESIA EXTENSION TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
39
Purpose
Capital Improvement Program Assesment
Project
20170720VMR_ARTESIA_EXTENSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0024
Downstream MH
02 0025
Dir. of Survey
Upstream
Length Surveyed
330.5 ft.
Total Length
330.5 ft.
Structural Index
2
Structural Quick
3526
Structural Rating
41
O&M Index
2
O&M Quick
2400
O&M Rating
8
Overall Index
2
Overall Quick
Overall Rating
49
Pipe schematic from manhole 02 0024 to 02 0025
MH: 02 0024MH: 02 0025upstream0 ft. AMH - Upstream Manhole, Survey Ends - 03:50 AM16.6 ft. CC - Crack Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES31.8 ft. CC - Crack Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES41 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES52.9 ft. CC - Crack Circumferential, from 11 to 03 o'clock, within 8 inches of joint: YES67.8 ft. CC - Crack Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES70.4 ft. CC - Crack Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES83.7 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 4"86.3 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 4"93.6 ft. CM - Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES99.6 ft. CC - Crack Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES114.6 ft. CC - Crack Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES168.2 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES177.5 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, at 09 o'clock, , within 8 inches of joint: YES178.5 ft. TBI - Tap Break-In Intruding, at 11 o'clock, -, -, within 8 inches of joint: YES, 4", 3"180 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES180.5 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 4"182.7 ft. CM - Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES186 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES187 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4"189.8 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 4"192.8 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 4", 4"194.9 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES200.2 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES203.2 ft. CC - Crack Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES212.1 ft. CC - Crack Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES218.3 ft. CC - Crack Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES221.2 ft. CC - Crack Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES225 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 4", 4"241.9 ft. CC - Crack Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES261 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 4"271.5 ft. CC - Crack Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES286.9 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, at 09 o'clock, , within 8 inches of joint: YES286.9 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, at 03 o'clock, , within 8 inches of joint: YES287.6 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"298.1 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES298.1 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES301.2 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES313.6 ft. CC - Crack Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES330.5 ft. MWM - Water Mark, 40 %of cross sectional area330.5 ft. AMH - Downstream Manhole, Survey Begins - 02:45 AM330.5 ft. MWL - Water Level, 20 %of cross sectional area

Observation photos (4)

  • Deposits Attached Grease, 10 %of cross sectional area, at 09 o'clock,  , within 8 inches of joint: YES

    43.6 ft. - Deposits Attached Grease, 10 %of cross sectional area, at 09 o'clock, , within 8 inches of joint: YES

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 4", 4"

    105.5 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 4", 4"

  • Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4"

    143.5 ft. - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4"

  • Deposits Attached Grease, 10 %of cross sectional area, at 09 o'clock,  , within 8 inches of joint: YES

    153 ft. - Deposits Attached Grease, 10 %of cross sectional area, at 09 o'clock, , within 8 inches of joint: YES

Observations (42)

DistanceCodeObservation
43.6DAGS
29.3CL
262.7CC
215.9CC
289.5CM
105.5TBA
144.5CM
127.3CC
140.7TFC
330.5AMH03:50 AM
109.3CC
236.9CM
152TBI
246.8TF
150TBA
277.6CC
260.1CC
230.9CC
298.7CC
32.4CL
88.6CC
143.5TFC
32.4CL
162.3CL
69.5TFC
118.4CC
59CC
112.2CC
150.5CM
0MWM
313.9CC
42.9TFA
130.3CL
43.6DAGS
153DAGS
147.8CM
0AMH02:45 AM
0MWL
244.2TF
16.9CC
135.6CL
137.7TBA

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2017-07-20T00:30:47-07:00
documentation
REVELES,MANANES,OLIVER
is_lateral_inspection
false