Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 20, 2017, 07:06 AM
  • 02 0027_02 0026_7202017_003254.mp4

Date
07/20/2017
W/O
0641143
Weather
Dry
Operator/Surveyor
REVELES
Sewer ID
Z00234
PipeID
P03058
Time
12:06 AM
Certificate
U-11506022630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0596
Sewer Name
02 ARTESIA EXTENSION TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
39
Purpose
Capital Improvement Program Assesment
Project
20170720VMR_ARTESIA_EXTENSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 0027
Downstream MH
02 0026
Dir. of Survey
Downstream
Length Surveyed
338.7 ft.
Total Length
338.7 ft.
Structural Index
1
Structural Quick
3221
Structural Rating
16
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
1
Overall Quick
Overall Rating
16
Pipe schematic from manhole 02 0027 to 02 0026
MH: 02 0027MH: 02 0026downstream-8.8 ft. CC - Crack Circumferential, from 09 to 10 o'clock, within 8 inches of joint: NO0 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:10 AM0 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 4"41.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES47.9 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 4"50.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4"54.8 ft. CM - Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES69.3 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 4" - Open129.5 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES144.4 ft. CC - Crack Circumferential, from 09 to 01 o'clock, within 8 inches of joint: YES145.7 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 4"147.6 ft. CC - Crack Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES148.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4"203.2 ft. CC - Crack Circumferential, from 10 to 11 o'clock, within 8 inches of joint: YES242.3 ft. CC - Crack Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES246.6 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 4"249.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"253.4 ft. CC - Crack Circumferential, from 10 to 11 o'clock, within 8 inches of joint: YES298.1 ft. CC - Crack Circumferential, from 09 to 02 o'clock, within 8 inches of joint: YES310 ft. CC - Crack Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES329.9 ft. AMH - Downstream Manhole, Survey Ends - 12:58 AM

Observation photos (1)

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 4" - Open

    69.3 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 4" - Open

Observations (24)

DistanceCodeObservation
242.3CC
0TFC
144.4CC
54.8CM
0MWM
329.9AMH12:58 AM
50.9TFC
129.5CL
0MWL
298.1CC
246.6TF
69.3TBOpen
203.2CC
147.6CC
0AMH12:10 AM
-8.8CC
0TFA
249.2TFC
41.2CM
253.4CC
47.9TFC
145.7TF
148.7TFC
310CC

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2017-07-20T00:06:00-07:00
documentation
REVELES,MANANES,OLIVER
is_lateral_inspection
false