Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 22, 2019, 11:40 AM
  • Section#5_16 0273_16 0272__7222019__I0185R.mp4

Date
07/22/2019
W/O
0777342
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00652
PipeID
P13315
Time
4:40 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0185R
Sewer Name
16 CHAPEL AVENUE TRUNK, SECTION 1
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
17
Purpose
Maintenance Related
Project
20190722MDM_CHAPEL_AVENUE_TRUNK_SECTION_1
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
16 0273
Downstream MH
16 0272
Dir. of Survey
Downstream
Length Surveyed
199.6 ft.
Total Length
199.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3B24
O&M Rating
63
Overall Index
2
Overall Quick
Overall Rating
63
Pipe schematic from manhole 16 0273 to 16 0272
MH: 16 0273MH: 16 0272downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - MH CONN 9:00 ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 4:45AM0 ft. MWL - Water Level, 10 %of cross sectional area16.9 ft. RFJ - Roots Fine Joint, from 08 to 09 o'clock, within 8 inches of joint: YESR - 2%19.8 ft. RMJ - Roots Medium Joint, from 02 to 05 o'clock, 10 %, within 8 inches of joint: YESR28.3 ft. RMJ - Roots Medium Joint, from 03 to 05 o'clock, 5 %, within 8 inches of joint: YESR49.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - STUB64.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB70.7 ft. RFJ - Roots Fine Joint, from 08 to 09 o'clock, within 8 inches of joint: YESR - 2%76 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - STUB82.2 ft. RMJ - Roots Medium Joint, from 03 to 04 o'clock, 5 %, within 8 inches of joint: YESR90.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB102 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN-80% ROOTS102 ft. RFL - Roots Fine Lateral, from 08 to 10 o'clock - 3%102.7 ft. RFJ - Roots Fine Joint, from 08 to 10 o'clock, within 8 inches of joint: YESR - 3%105.8 ft. RMJ - Roots Medium Joint, from 03 to 09 o'clock, 15 %, within 8 inches of joint: YESR110.4 ft. RFJ - Roots Fine Joint, from 03 to 09 o'clock, within 8 inches of joint: YESR - 3%113.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB114.6 ft. RFJ - Roots Fine Joint, from 03 to 04 o'clock, within 8 inches of joint: YESR - 2%117.8 ft. RMJ - Roots Medium Joint, from 02 to 05 o'clock, 10 %, within 8 inches of joint: YESR125.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - STUB125.1 ft. RMJ - Roots Medium Joint, from 03 to 05 o'clock, 5 %, within 8 inches of joint: YESR129.8 ft. RMJ - Roots Medium Joint, from 02 to 10 o'clock, 15 %, within 8 inches of joint: YESR135.5 ft. RMJ - Roots Medium Joint, from 02 to 05 o'clock, 10 %, within 8 inches of joint: YESR137.5 ft. RTL - Roots Tap Lateral, from 02 to 05 o'clock, 5 %, within 8 inches of joint: YES137.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB140.7 ft. RMJ - Roots Medium Joint, from 03 to 09 o'clock, 5 %, within 8 inches of joint: YESR143.9 ft. RFJ - Roots Fine Joint, from 08 to 09 o'clock, within 8 inches of joint: YESR - 2%152.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - STUB155.2 ft. RMJ - Roots Medium Joint, from 02 to 05 o'clock, 10 %, within 8 inches of joint: YESR158.2 ft. RMJ - Roots Medium Joint, from 02 to 05 o'clock, 15 %, within 8 inches of joint: YESR163.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB164.7 ft. RMJ - Roots Medium Joint, from 02 to 10 o'clock, 30 %, within 8 inches of joint: YESR174 ft. RMJ - Roots Medium Joint, from 02 to 05 o'clock, 5 %, within 8 inches of joint: YESR175.8 ft. RMJ - Roots Medium Joint, from 02 to 05 o'clock, 15 %, within 8 inches of joint: YESR175.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN186.8 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN 95% ROOTS186.8 ft. RMJ - Roots Medium Joint, from 03 to 09 o'clock, 5 %, within 8 inches of joint: YESR186.8 ft. RTL - Roots Tap Lateral, from 02 to 04 o'clock, 5 %, within 8 inches of joint: YES189 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 65" - OPEN191 ft. RMJ - Roots Medium Joint, from 03 to 09 o'clock, 15 %, within 8 inches of joint: YESR199.6 ft. AMH - Downstream Manhole, Survey Ends - 5:15AM

Observation photos (8)

  • Roots Medium Joint, from 02 to 05 o'clock, 10 %, within 8 inches of joint: YESR

    19.8 ft. - Roots Medium Joint, from 02 to 05 o'clock, 10 %, within 8 inches of joint: YESR

  • Roots Medium Joint, from 03 to 05 o'clock, 5 %, within 8 inches of joint: YESR

    28.3 ft. - Roots Medium Joint, from 03 to 05 o'clock, 5 %, within 8 inches of joint: YESR

  • Roots Medium Joint, from 03 to 09 o'clock, 15 %, within 8 inches of joint: YESR

    105.8 ft. - Roots Medium Joint, from 03 to 09 o'clock, 15 %, within 8 inches of joint: YESR

  • Roots Medium Joint, from 02 to 10 o'clock, 15 %, within 8 inches of joint: YESR

    129.8 ft. - Roots Medium Joint, from 02 to 10 o'clock, 15 %, within 8 inches of joint: YESR

  • Roots Medium Joint, from 02 to 05 o'clock, 15 %, within 8 inches of joint: YESR

    158.2 ft. - Roots Medium Joint, from 02 to 05 o'clock, 15 %, within 8 inches of joint: YESR

  • Roots Medium Joint, from 02 to 10 o'clock, 30 %, within 8 inches of joint: YESR

    164.7 ft. - Roots Medium Joint, from 02 to 10 o'clock, 30 %, within 8 inches of joint: YESR

  • Roots Medium Joint, from 02 to 05 o'clock, 15 %, within 8 inches of joint: YESR

    175.8 ft. - Roots Medium Joint, from 02 to 05 o'clock, 15 %, within 8 inches of joint: YESR

  • Roots Medium Joint, from 03 to 09 o'clock, 15 %, within 8 inches of joint: YESR

    191 ft. - Roots Medium Joint, from 03 to 09 o'clock, 15 %, within 8 inches of joint: YESR

Observations (43)

DistanceCodeObservation
0MWM
114.6RFJ2%
82.2RMJ
137.5RTL
191RMJ
64.6TFCSTUB
186.8TFDOPEN 95% ROOTS
155.2RMJ
152.2TFCSTUB
189TBOPEN
158.2RMJ
90.3TFCSTUB
125.1TFCSTUB
102.7RFJ3%
186.8RMJ
143.9RFJ2%
0MGOMH CONN 9:00 ACTIVE
175.8RMJ
0AMH4:45AM
0MWL
137.5TFCSTUB
125.1RMJ
19.8RMJ
102TFDOPEN-80% ROOTS
49.7TFCSTUB
140.7RMJ
16.9RFJ2%
186.8RTL
174RMJ
70.7RFJ2%
164.7RMJ
113.9TFCSTUB
28.3RMJ
76TFCSTUB
163.4TFCSTUB
105.8RMJ
102RFL3%
117.8RMJ
135.5RMJ
199.6AMH5:15AM
110.4RFJ3%
175.8TFOPEN
129.8RMJ

Properties (5)

additional_info
ROOT EVALUATION ONLY
customer
LACSD
datetime
2019-07-22T04:40:30-07:00
documentation
MARTIN,REVELES,OLIVER 111,SHADLER
is_lateral_inspection
false