Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 17, 2019, 12:06 PM
  • Section#7_02 1110_02 1109__7172019__I0178.mp4

Date
07/17/2019
W/O
0776968
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00285
PipeID
P04601
Time
5:06 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0178
Sewer Name
02 MONTEBELLO-RANDOLPH TRUNK
City
BELL GARDENS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
20
Purpose
Routine Assessment
Project
20190717MDM_MONTEBELLO_RANDOLPH_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
02 1110
Downstream MH
02 1109
Dir. of Survey
Downstream
Length Surveyed
292.3 ft.
Total Length
292.3 ft.
Structural Index
3
Structural Quick
413R
Structural Rating
480
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
480
Pipe schematic from manhole 02 1110 to 02 1109
MH: 02 1110MH: 02 1109downstream0 ft. AMH - Upstream Manhole, Survey Begins - 5:10AM0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area4.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT8.5 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - HAIRLINE15.2 ft. FC - Fracture Circumferential, from 09 to 02 o'clock, within 8 inches of joint: YES - SL18.2 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SL21.5 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS21.5 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS21.5 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS21.5 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS48.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB179.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB186.5 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN255.2 ft. MGO - General Observation - 292.34 FOOTAGE ADJUST255.2 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - 10% SLIGHT AT JOINTS255.2 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - 10% SLIGHT AT JOINTS255.2 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 355 HAIRLINE AT JOINTS255.2 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 35% SLIGHT AT JOINTS292.3 ft. AMH - Downstream Manhole, Survey Ends - 5:35AM

Observation photos (1)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT

    4.8 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT

Observations (20)

DistanceCodeObservation
8.5FCHAIRLINE
4.8FMSLIGHT
15.2FCSL
255.2MGO292.34 FOOTAGE ADJUST
255.2FL10% SLIGHT AT JOINTS
0AMH5:10AM
255.2FL10% SLIGHT AT JOINTS
186.5TBOPEN
292.3AMH5:35AM
18.2FCSL
21.5FLHAIRLINE AT JOINTS
21.5FCHAIRLINE AT JOINTS
0MWM
179.1TFCSTUB
21.5FLSLIGHT AT JOINTS
0MWL
255.2FC355 HAIRLINE AT JOINTS
255.2FC35% SLIGHT AT JOINTS
21.5FCSLIGHT AT JOINTS
48.2TFCSTUB

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2019-07-17T05:06:16-07:00
documentation
MARTIN,REVELES,OLIVER 111,SHADLER
is_lateral_inspection
false