Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 17, 2019, 11:21 AM
  • Section#6_02 1111_02 1110__7172019__I0178.mp4

Date
07/17/2019
W/O
0776968
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00285
PipeID
P04602
Time
4:21 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0178
Sewer Name
02 MONTEBELLO-RANDOLPH TRUNK
City
BELL GARDENS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
20
Purpose
Routine Assessment
Project
20190717MDM_MONTEBELLO_RANDOLPH_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
02 1111
Downstream MH
02 1110
Dir. of Survey
Downstream
Length Surveyed
365.1 ft.
Total Length
365.1 ft.
Structural Index
3
Structural Quick
413X
Structural Rating
632
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
632
Pipe schematic from manhole 02 1111 to 02 1110
MH: 02 1111MH: 02 1110downstream0 ft. AMH - Upstream Manhole, Survey Begins - 4:25AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area6.8 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - HAIRLINE13.7 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H17.4 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - SLIGHT17.4 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - SL21.1 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES - SL25 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS25 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS25 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS25 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS333.1 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 35% HAIRLINE AT JOINTS333.1 ft. MGO - General Observation - 365' FOOTAGE ADJUST333.1 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - 10% SLIGHT AT JOINTS333.1 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 50% SLIGHT AT JOINTS333.1 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - 10% HAIRLINE AT JOINTS365.1 ft. AMH - Downstream Manhole, Survey Ends - 5:00AM

Observations (18)

DistanceCodeObservation
333.1FC35% HAIRLINE AT JOINTS
25FCSLIGHT AT JOINTS
13.7FCH
17.4FCSLIGHT
21.1FMSL
0AMH4:25AM
365.1AMH5:00AM
6.8FCHAIRLINE
333.1MGO365' FOOTAGE ADJUST
17.4FCSL
25FLHAIRLINE AT JOINTS
0MWL
333.1FL10% SLIGHT AT JOINTS
25FCHAIRLINE AT JOINTS
0MWM
333.1FC50% SLIGHT AT JOINTS
25FLSLIGHT AT JOINTS
333.1FL10% HAIRLINE AT JOINTS

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2019-07-17T04:21:19-07:00
documentation
MARTIN,REVELES,OLIVER 111,SHADLER
is_lateral_inspection