Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 17, 2019, 10:17 AM
  • Section#5_02 1112_02 1111__7172019__I0177.mp4

Date
07/17/2019
W/O
0776968
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00285
PipeID
P04603
Time
3:17 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0177
Sewer Name
02 MONTEBELLO-RANDOLPH TRUNK
City
BELL GARDENS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
20
Purpose
Routine Assessment
Project
20190717MDM_MONTEBELLO_RANDOLPH_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
02 1112
Downstream MH
02 1111
Dir. of Survey
Downstream
Length Surveyed
231.4 ft.
Total Length
231.4 ft.
Structural Index
2
Structural Quick
382D
Structural Rating
76
O&M Index
2
O&M Quick
2G00
O&M Rating
76
Overall Index
2
Overall Quick
Overall Rating
152
Pipe schematic from manhole 02 1112 to 02 1111
MH: 02 1112MH: 02 1111downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:50AM2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING OUTER SURFACE4.4 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SLIGHT11.2 ft. SSS - Surface Spalling, from 12 to 03 o'clock, within 8 inches of joint: NO - BLLISTERING PEELING14 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SLIGHT26.1 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SL30 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start30 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SLIGHT34 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - HAIRLINE38.5 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SL42.1 ft. FC - Fracture Circumferential, from 11 to 03 o'clock, within 8 inches of joint: YES - SL43.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB52.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BLISTERING OUTER SURFACE56.9 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES - H60.6 ft. FC - Fracture Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES - SL75.5 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SL82.9 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H86.5 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H97.4 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H113.2 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL128.1 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL131.6 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H142.5 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL149.7 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H179.2 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H184.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB184.2 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H186.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H192.8 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H215.2 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H220.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish231.4 ft. AMH - Downstream Manhole, Survey Ends - 4:15AM

Observation photos (3)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING OUTER SURFACE

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING OUTER SURFACE

  • Surface Spalling, from 12 to 03 o'clock, within 8 inches of joint: NO - BLLISTERING PEELING

    11.2 ft. - Surface Spalling, from 12 to 03 o'clock, within 8 inches of joint: NO - BLLISTERING PEELING

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    30 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (34)

DistanceCodeObservation
34FCHAIRLINE
52.9SSSBLISTERING OUTER SURFACE
42.1FCSL
97.4FLH
215.2FLH
192.8FLH
131.6FCH
75.5FCSL
56.9FLH
0MWL
149.7FLH
184.2TFCSTUB
30DAGS
2SSSBLISTERING OUTER SURFACE
26.1FCSL
60.6FCSL
82.9FCH
128.1FCSL
179.2FLH
0MWM
38.5FCSL
14FCSLIGHT
4.4FCSLIGHT
184.2FLH
220.6DAGS
43.3TFCSTUB
142.5FCSL
186.2FLH
231.4AMH4:15AM
30FCSLIGHT
113.2FCSL
0AMH3:50AM
86.5FCH
11.2SSSBLLISTERING PEELING

Properties (6)

custom_field_three
SLIGHT FRACTURES -SPALLING
custom_field_two
3
customer
LACSD
datetime
2019-07-17T03:17:05-07:00
documentation
MARTIN,REVELES,OLIVER 111,SHADLER
is_lateral_inspection
false